Trang chủ » PACs » Bộ lập trình nhúng PAC CPU x86 OS CE 6.0 nhúng Win-GRAF ICP DAS XP-8738-CE6 CR

Bộ lập trình nhúng PAC CPU x86 OS CE 6.0 nhúng Win-GRAF ICP DAS XP-8738-CE6 CR

7-slot Win-GRAF Based PAC with x86 CPU and WinCE 6.0

Chia sẻ:
Model: XP-8738-CE6 CR
Views: 2122

Bộ lập trình nhúng PAC CPU x86 OS CE 6.0 nhúng Win-GRAF ICP DAS XP-8738-CE6 CR

The Win-GRAF XPAC-8000-CE6 Series (XP-8038-CE6/XP-8138-CE6/XP-8338-CE6/XP-8738-CE6) is the new generation WinCE 6.0 based Win-GRAF XPAC-CE6 (Programmable Automation Controller) from ICP DAS. Each is equipped with an x86 CPU (1 GHz) dual-core running a Windows CE 6.0 operating system, a variety of input/output ports (VGA, USB, Ethernet, RS-232/485), and a range of I/O slots (0/1/3/7) that can be used to integrate high performance parallel I/O modules (high profile I-8K Series) or serial I/O modules (high profile I-87K series)

The benefits of running Windows CE 6.0 on a XPAC device include hard real-time capability, achievable deterministic control and allowing PAC can have a PC-like window displays and operating environment. The PACs are capable of running Win-GRAF (IEC 61131-3 Standard) software to develop logic control applications, and also supporting M.S. VS 2008 software (VB .NET, C#) to develop HMI and data management applications that can exchange data with Win-GRAF applications. So the application’s design is more convenient and more practical.

  • Redundancy

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
1. Near-Field Redundancy

Refer to Win-GRAF User Manual: Chapter 16

Win-GRAF_Redundancy-Near_Field
2. Far-Field Redundancy

Refer to Win-GRAF User Manual: Chapter 16

Win-GRAF_Redundancy-Far_Field
  • eLogger HMI

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
eLogger is a free of charge and an easy-to-use HMI software platform developed by ICP DAS. It can be used to design the Local HMI and the Web Server HMI for remotely controlling the PAC through a web browser on your PC or cell phone.

Refer to Win-GRAF User Manual: Chapter 15

  • On-Line Change

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
Replace the current running project to a new modified one without stopping the project.

Refer to Win-GRAF User Manual: Chapter 9

  • Schedule Control

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
* One PAC can control up to 10 Targets (devices) with specified schedule configurations.
* One BOOL variable, one DINT variable, and one REAL variable can be used for each schedule Target.Refer to Win-GRAF User Manual: Chapter 17
Win-GRAF_Schedule_Control
  • Create Your Own Functions and Function Blocks

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
* For some reason, like business protection or the integration of custom protocol for products. Users can develop their own functions and function blocks by using VS 2008 and then use these functions (blocks) in the Win-GRAF project.

Refer to Win-GRAF User Manual: Chapter 18

  • Modbus Master/Slave Protocol

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
* The following Modbus protocols are supported for Win-GRAF PACs.

  • Modbus TCP/IP Master
  • Modbus TCP/IP Slave
  • Modbus RTU/ASCII Master
  • Modbus RTU Slave

Refer to Win-GRAF User Manual: Chapter 3 and Chapter 5

  • DCON Remote I/O

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
* Win-GRAF PACs support to connect DCON remote I/O modules via RS-485 port.

Refer to Win-GRAF User Manual: Chapter 8

  • PID Control

Model XP-8×38-CE6 WP-8×28-CE7 WP-5238-CE7 VP-x208-CE7 VP-x238-CE7
Support
* A single Win-GRAF PAC supports 200 PID control.

Refer to Win-GRAF User Manual: Chapter 12 (PID Demo)

Software
OS Windows CE 6.0
Protocol • NET ID
• Redundancy Solution
• eLogger HMI
• Modbus TCP/IP Master
• Modbus TCP/IP Slave
• Modbus RTU/ASCII Master
• Modbus RTU Slave
• DCON Protocol
• User-defined Protocol
• I/O Type: DCON, Modbus RTU, and Modbus TCP/IP remote I/O
• Local I/O Modules
• Application Protection
• Data Binding
• On Line Change
• HART Master Protocol
• Schedule Control
• Retain Variables
• File Access and Data Log
Development Embedded Win-GRAF SoftLogic (IEC 61131-3)
Service FTP Server, ASP (Java Script, VB Script), SQL Compact Edition 3.5
Framework Support .Net Compact Framework 3.5
Multilanguage Support English, German, French, Spanish, Portuguese, Russian, Italian, Korean, Japanese, Simplified Chinese, Traditional Chinese
SDK Dll for eVC, Dll for Visual Studio.Net 2005/2008
Main Unit
CPU x86 CPU, 1.0 GHz, dual-core
64-bit Hardware Serial Number Yes
System Memory 2 GB DDR3 SDRAM
Non-Volatile Memory 16 KB EEPROM, 512 KB MRAM
Storage 32 GB Flash, 8 GB CF card (up to 32 GB)
Real Time Clock Provide seconds, minutes, hours, dates, day of week, month, year
Watchdog Timer Dual Watchdog Timer
Display
Signal VGA
Resolution 640 × 480, 800 × 480, 800 × 600, 1024 × 768
LED Indicators
Status 1 x System, 1 x Power, 2 x Programmable
I/O Expansion
I/O Type I-8K, I-87K series
Slots 7
COM Ports
Ports 2 x RS-232, 1 x RS-485 (3000 VDC Isolated), 1 x RS-232/RS-485
HMI
Buzzer Yes
Rotary Switch 1 x 10 Position (0 ~ 9)
DIP Switch 8-bit for address
Audio
Cable Microphone-In and Earphone-Out
Ethernet
Ports 2 x RJ-45, 10/100/1000 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators)
USB
Ports 4 x USB 2.0
Power
Input Range +10 ~ 30 VDC (1 kV Isolated )
Redundant Power Inputs Yes
Consumption 18.0 W
Mechanical
Casing Plastic
Dimensions (mm) 355 x 132 x 125 (W x L x H)
Installation DIN-Rail, Wall mounting
Ingress Protection Rating IP30 (Aluminum)
Environmental
Operating Temperature -25 ~ +75°C
Storage Temperature -30 ~ +80°C
Humidity 10 ~ 90% RH, Non-condensing

Specification Memo

Note: COM6 ~ COM33 ports are located in the expansion boards (I-8142iW, I-8144iW, I-8112iW, I-8114W, I-8114iW) if they are installed in slot 1 ~ 7 of XP-8×38-CE6
XP-8738-CE6     CR 7-slot Win-GRAF Based PAC with x86 CPU and WinCE 6.0 (RoHS)