Intelligent I/O Module with 6-ch DI and 6-ch Power Relay

Model: WISE-7160 CR

Views: 474
Đánh giá bài viết
Chia sẻ:
Introductions

Bộ điều khiển IIoT Ethernet 6 kênh DI+6 kênh đầu ra Relay ICP DAS WISE-7160 CR

WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.

WISE-7160 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7160 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.

This module WISE-7160 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It features 6 power relay outputs and 6 isolated wet contact digital inputs. Each power relay supports contact rating as 5 A @ 250 VAC or 5 A @ 30 VDC and each digital input channel supports counter input.

TOP HOME
Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.

TOP HOME
Hardware Specifications
Digital Input
Input Channels 6
Input Type Wet Contact (Sink, Source)
On Voltage Level +10 VDC ~ +50 VDC
Off Voltage Level +4 VDC Max.
Input Impedance 10 kΩ
Counters Max. Count 65535 (16 bits)
Max. Input Frequency 50 Hz
Min. Pulse Width 10 ms
Overvoltage Protection +70 VDC
Power Relay
Output Channels 6
Output Type Power Relay, Form A (SPST N.O.)
Operating Voltage Range 250 VAC/30 VDC
Max. Load Current 5.0 A/channel at 25 °C
Operate Time 6 ms (Typical)
Release Time 3 ms (Typical)
Electrical Life
(Resistive Load)
VDE 5A 250 VAC 30,000 ops (10 ops/minute) at 75 °C
5A 30 VDC 70,000 ops (10 ops/minute) at 75 °C
UL 5A 250 VAC/30 VDC 6,000 ops.
3A 250 VAC/30 VDC 10,000 ops.
Mechanical Life 20,000,000 ops. at no load (300 ops./minute)
System
CPU 16-bit CPU
SRAM 512 KB
Flash Memory 512 KB
EEPROM 16 KB
Watchdog Yes
Communication
PoE Ethernet Port 10 / 100 Base-TX and automatic MDI/MDI-X
2 Way Isolation
I/O 2500 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±2 kV for Power Line
LED Indicators
PoE PoE On
L1 System Running
L2 Ethernet Link/Act
L3 Ethernet 10/100M Speed
Power Requirements
Reserve Polarity Protection Yes
Powered from terminal block Yes, 12 ~ 48 VDC
Powered from PoE Yes, IEEE 802.3af, Class1
Consumption 4.8 W
Mechanical
Dimensions (W x H x D) 72 mm x 123 mm x 35 mm
Installation DIN-Rail or Wall mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +80 °C
Humidity 10 ~ 90% RH, non-condensing
TOP HOME
Functions
Rule Configuration Website Access Web server on WISE controllers to edit and upload logic rules through web browser.
36 IF-THEN-ELSE Logic Rules 3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions
48 Internal Registers Hold temporary variables and read/write data via Modbus/TCP address.
12 Timers Delay / Timing functions.
12 Emails Send Email messages to pre-set Email receivers.
12 CGI Commands Send pre-set CGI commands.
12 Recipes Set up THEN/ELSE action groups.
8 P2P remote modules Set up the connection information for the remote WISE modules.
Modbus/TCP Protocol Real time control and monitoring I/O channels and system status of controllers via SCADA software.
IF Conditions
DI Channel ON、OFF、ON to OFF、OFF to ON、Change
Internal Register = 、> 、< 、 ≥ 、 ≤ (value)
DI Counter = 、> 、< 、 ≥ 、 ≤ (value)、Change
DO Counter
Timer Timeout、Not Timeout
P2P DI、AI、DI counter、DO counter、IR
Rule Status Enable、Disable
THEN / ELSE Actions
DO Channel ON、OFF、Pulse Output
Internal Register Change the value
DI Counter Reset
DO Counter
Timer Start、Stop
Email Send
CGI Commands
Recipe Execute
P2P DO(On/Off)、AO、IR
Rule Status Enable、Disable
TOP HOME
Odering Informations
WISE-7160     CR Intelligent I/O Module with 6-ch DI, 6-ch Power Relay and PoE (RoHS)
TOP HOME