Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module I/O OPC UA & MQTT 16 kênh đầu ra số DO ICP DAS U-7542M CR

Module I/O OPC UA & MQTT 16 kênh đầu ra số DO ICP DAS U-7542M CR

OPC UA I/O Module with 16-channels DO and 2-port Ethernet Switch

Chia sẻ:
Model: U-7542M CR
Views: 857

U-7542M is a UA I/O module that provides 16 digital output channels. It has a built-in dual-port Ethernet switch to implement daisy-chain topology. The cabling is much easy and can reduce the total cable and switch cost. It follows IEEE 802.3af (Class 2) compliant Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs. This feature provides greater flexibility and efficiency to simplify system design, save space, and reduce wirings and power sockets. It provides a Web UI to confi gure/control/monitor the modules, connections, and I/O status via a web browser. It is easy, fast, and no extra APP needed.

In industrial communication, UA I/O provides OPC UA Server / Client, MQTT Client and RESTful API protocols (can execute all communications at the same time.). Users can choose the networking mode according to their cases. And to transmit the values of the built-in I/O channels to the Cloud system or field control system for displaying, analysis or strategy. Support Scaling. Let the analog signal be converted into a more readable value. Support logic function Rule Setting IF, THEN, ELSE, can set up logical condition/action for I/O and virtual point; Provide schedule function to execute the set rules at a specific time; Support RESTful API function, can read/write I/O and virtual point through HTTP or HTTPS

UA I/O Series provides a Web-based User Interface (Web UI) to configure the module, control the output channels, monitor the connection, and I/O status via a normal web browser. It is easy, fast, and no extra APP needed.

OPC UA Architecture:

MQTT Architecture:

  • Built-in OPC UA Server Service

Compliance with IEC 62541 Standard. Provides functions of Active Transmission, Transmission Security Encryption ( SSL / TLS ), User Authentication (X.509 Certificates / Account password), Communication Error Detection and Recovery, etc. to connect SCADA or OPC UA Clients. Recommend to keep the maximum number of sessions within 3 connections.

  • Built-in OPC UA Client Service

Compliance with IEC 62541 Standard. Provides Transmission Security Encryption ( SSL / TLS ), User Authentication (X.509 Certificates / Account password) and OPC UA Server Connectivity.

  • Built-in MQTT Client Service

Build-in MQTT Client Service (Compliance with MQTT V.3.1.1 protocol). Provides functions of IoT Active M2M Transmission, QoS (Quality of Service), Retains Mechanism, Identity Authentication, Encryption, Last Will, etc.

  •  RESTful API 
Can read/write I/O and virtual point through HTTP.
Provide high-security HTTPS (identity verification and communication encryption) to read/write I/O and Virtual points.
  • Execute OPC UA , MQTT, and RESTful API Communication at the Same Time

  • Support IoTstar Cloud Management Software

UA I/O factory version 9.7 and later supports this function.

  • Scaling Function for Improved Readability

AI/AO modules support Scaling. Let the analog signal be converted into a more readable value.

  • Support Logic Function Rule Setting: IF, THEN, ELSE  

Users can set up logical condition/action for I/O and virtual point.

  • Support Schedule   

Provide schedule function to execute the set rules at a specific time.

  • Support Trigger Message 

When the I/O value changes, the message can be recorded in a file (CSV) and sent to Line for easy device tracking in the future.

  • Built-in Web Server to Provide the Web User Interface

UA I/O Series provides a Web-based User Interface (Web UI) to configure the module, control the output channels, monitor the connection, and I/O status via a normal web browser. It is easy, fast, and no extra APP needed.

  • Diversified Choices

Different models provide different AI, AO, DI, or DO channels, and users can choose the desired model according to the needs of the case.

  • Dual-port Ethernet Switch for Daisy-Chain Topology

The cabling of Daisy-Chain Topology is much easier and total costs of cable and switch are significantly reduced.

  • IEEE 802.3af-compliant Power over Ethernet (PoE)

UA I/O follows IEEE 802.3af (classification, Class 2) compliant Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs. This feature provides greater flexibility and efficiency to simplify system design, save space, and reduce wirings and power sockets.

Software
Protocol • OPC UA Server / Client
• MQTT Client
• RESTful API
Function • Web Interface for Configuration
• Scaling
• Security
• Rule Setting
• Schedule
• Event Log
• IoTstar Setting
CPU Module
CPU 32-bit CPU (400 MHz)
Watchdog Timer Module, Communication (Programmable)
Isolation
2-way Isolation I/O: 3750 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal
±8 kV Air for random point
Surge (IEC 61000-4-5) ±2 kV for Power Line
LED Indicators
Status Run, Ethernet, I/O
Digital Output
Channels 16
Type Isolated Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage + 3.5 ~ + 50 VDC
Load Current 650 mA/channel at 25°C
Direct Drive Power Relay Module
Overvoltage Protection +60 VDC
Overload Protection 1.3 A
Short-circuit Protection Yes
Power on Value Programmable
Safe Value Programmable
Ethernet
Ports 2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoE Yes
LAN bypass Yes
Access Control ID, Password and IP Filter
Power
Reverse Polarity Protection Yes
Consumption 5.9 W
Powered from PoE IEEE 802.3af, Class3
Powered from Terminal Block +12 ~ +48 VDC
Mechanical
Dimensions (mm) 97 x 120 x 47 (W x L x H)
Installation DIN-Rail mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
U-7542M     CR  OPC UA I/O Module with 16-channels DO and 2-port Ethernet Switch. (RoHS)