Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module I/O OPC UA & MQTT 2 kênh DI + 2 kênh DO + 6 kênh AI + 2 kênh AO ICP DAS U-7526M CR

Module I/O OPC UA & MQTT 2 kênh DI + 2 kênh DO + 6 kênh AI + 2 kênh AO ICP DAS U-7526M CR

OPC UA I/O Module with 2-ch DI, 2-ch DO, 6-ch AI, 2-ch AO, and 2-port Ethernet Switch

Chia sẻ:
Model: U-7526M CR
Views: 843

U-7526M is a UA I/O module that provides 2 digital input channels, 2 digital output channels, 6 analog input channels and 2 analog output. It has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easy and can reduce the total cable and switch cost. It follows IEEE 802.3af (Class 2) compliant Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs. This feature provides greater flexibility and efficiency to simplify system design, save space, and reduce wirings and power sockets. It provides a Web UI to configure/control/monitor the modules, connections, and I/O status via a web browser. It is easy, fast, and no extra APP needed.

In industrial communication, UA I/O provides OPC UA Server / Client, MQTT Client and RESTful API protocols (can execute all communications at the same time.). Users can choose the networking mode according to their cases. And to transmit the values of the built-in I/O channels to the Cloud system or field control system for displaying, analysis or strategy. Support Scaling. Let the analog signal be converted into a more readable value. Support logic function rule setting IF, THEN, ELSE, can set up logical condition/action for I/O and virtual point; Provide schedule function to execute the set rules at a specific time; and support RESTful API function, can read/write I/O and virtual point through HTTP or HTTPS.

UA I/O Series provides a Web-based User Interface (Web UI) to configure the module, control the output channels, monitor the connection, and I/O status via a normal web browser. It is easy, fast, and no extra APP needed.

OPC UA Architecture:

MQTT Architecture:

  • Built-in OPC UA Server Service

Compliance with IEC 62541 Standard. Provides functions of Active Transmission, Transmission Security Encryption ( SSL / TLS ), User Authentication (X.509 Certificates / Account password), Communication Error Detection and Recovery, etc. to connect SCADA or OPC UA Clients. Recommend to keep the maximum number of sessions within 3 connections.

  • Built-in OPC UA Client Service

Compliance with IEC 62541 Standard. Provides Transmission Security Encryption ( SSL / TLS ), User Authentication (X.509 Certificates / Account password) and OPC UA Server Connectivity.

  • Built-in MQTT Client Service

Build-in MQTT Client Service (Compliance with MQTT V.3.1.1 protocol). Provides functions of IoT Active M2M Transmission, QoS (Quality of Service), Retains Mechanism, Identity Authentication, Encryption, Last Will, etc.

  •  RESTful API 
Can read/write I/O and virtual point through HTTP.
Provide high-security HTTPS (identity verification and communication encryption) to read/write I/O and Virtual points.
  • Execute OPC UA , MQTT, and RESTful API Communication at the Same Time

  • Support IoTstar Cloud Management Software

UA I/O factory version 9.7 and later supports this function.

  • Scaling Function for Improved Readability

AI/AO modules support Scaling. Let the analog signal be converted into a more readable value.

  • Support Logic Function Rule Setting: IF, THEN, ELSE  

Users can set up logical condition/action for I/O and virtual point.

  • Support Schedule   

Provide schedule function to execute the set rules at a specific time.

  • Support Trigger Message 

When the I/O value changes, the message can be recorded in a file (CSV) and sent to Line for easy device tracking in the future.

  • Built-in Web Server to Provide the Web User Interface

UA I/O Series provides a Web-based User Interface (Web UI) to configure the module, control the output channels, monitor the connection, and I/O status via a normal web browser. It is easy, fast, and no extra APP needed.

  • Diversified Choices

Different models provide different AI, AO, DI, or DO channels, and users can choose the desired model according to the needs of the case.

  • Dual-port Ethernet Switch for Daisy-Chain Topology

The cabling of Daisy-Chain Topology is much easier and total costs of cable and switch are significantly reduced.

  • IEEE 802.3af-compliant Power over Ethernet (PoE)

UA I/O follows IEEE 802.3af (classification, Class 2) compliant Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs. This feature provides greater flexibility and efficiency to simplify system design, save space, and reduce wirings and power sockets.

Software
Protocol • OPC UA Server / Client
• MQTT Client
• RESTful API
Function • Web Interface for Configuration
• Scaling
• Security
• Rule Setting
• Schedule
• Event Log
• IoTstar Setting
CPU Module
CPU 32-bit CPU (400 MHz)
Watchdog Timer Module, Communication (Programmable)
Isolation
2-way Isolation I/O: 2500 VDC
EMS Protection
EFT (IEC 61000-4-4) ±2 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal
±8 kV Air for random point
Surge (IEC 61000-4-5) ±2 kV for Power Line
LED Indicators
Status Run, Ethernet, I/O
Analog Input
Channels 6 (Differential)
Type Voltage, Current
Range ±500 mV, ±1V, ±5 V, ±10 V
0 to 20 mA, ±20 mA, 4 to 20 mA
(Jumper Selectable)
Resolution 16-bit
Accuracy Normal Mode: ±0.1%
Fast Mode: ±0.5% or better
Sampling Rate Normal Mode: 10 samples/second (Total)
Fast Mode: 50 samples/second (Total)
Input Impedance Voltage: 2 MΩ
Current: 125 Ω
Common Mode Rejection 86 dB (min.)
Normal Mode Rejection 100 dB
Common Voltage Protection ±200 VDC
Overvoltage Protection 240 Vrms
Overcurrent Protection 50 mA at 110 VDC (max.)
Individual Channel Configuration Yes
Open Wire Detection For 4 ~ 20 mA only
Zero Drift ±20 μV/°C
Span Drift ±25 ppm/°C
Isolation ±400 VDC, Virtual Channel to Channel Isolation
Analog Output
Channels 2
Type Voltage, Current
Range +0 to +5 VDC, ±5 VDC, +0 to +10 VDC,
±10 VDC, 0 to 20 mA, 4 to 20 mA
(Jumper Selectable)
Resolution 12-bit
Accuracy ±0.1% of FSR
Open Wire Detection For 4 ~ 20 mA only
Voltage Output Capability 10 V @ 20 mA
Current Load Resistance 500 Ω
Individual Channel Configuration Yes
Power-on Value Programmable
Safe Value Programmable
Digital Input/Counter
Channels 2
Type Dry Contact
Wet Contact
ON Voltage Level Dry: Close to GND
Wet: +1 VDC (max.)
OFF Voltage Level Dry: Open
Wet: +3.5 to +30 VDC
Max. Counts 4,294,967,295 (32-bit)
Frequency 100 Hz
Min. Pulse Width 5 ms
Effective Distance 500m (max.)
Overvoltage Protection +30 VDC
Digital Output
Channels 2
Type Isolated Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +5 ~ +50 VDC
Load Current 700 mA/Channel
Overvoltage Protection +60 VDC
Overload Protection 1.4 A
Short-circuit Protection Yes
Power on Value Programmable
Safe Value Programmable
Ethernet
Ports 2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoE Yes
LAN bypass Yes
Access Control ID, Password and IP Filter
Power
Reverse Polarity Protection Yes
Consumption 7.1 W
Powered from PoE IEEE 802.3af, Class3
Powered from Terminal Block +12 ~ +48 VDC
Mechanical
Dimensions (mm) 97 x 120 x 47 (W x L x H)
Installation DIN-Rail mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
U-7526M     CR  OPC UA I/O Module with 2-ch DI, 2-ch DO, 6-ch AI, 2-ch AO, and 2-port Ethernet Switch. (RoHS)