Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module RS-485 DCON & Modbus 8 kênh đầu vào số (DI) ICP DAS tM-P8 CR

Module RS-485 DCON & Modbus 8 kênh đầu vào số (DI) ICP DAS tM-P8 CR

8-channel Isolated Digital Input Module

Chia sẻ:
Model: tM-P8 CR
Views: 1227

Module RS-485 DCON & Modbus 8 kênh đầu vào số (DI) ICP DAS tM-P8 CR

The tM-P8 off ers 8 channels for digital input, each of which features photocoupler isolation. In addition, digital input can be either sinkor source-type using wire connections and all channels can be used as 16-bit counters. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided. The tM-PDW8 off ers 8 channels for digital input, catering for both dry and wet contact, with an eff ective distance for dry contact of up to 500 meters. All channels not only feature Photocoupler isolation, but can also be used as 16-bit counters. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided.

  • Tất cả các loại điều khiển bật / tắt
  • Tự động hóa công nghiệp
  • Máy móc công nghiệp
  • Tự động hóa tòa nhà
  • Hệ thống thực phẩm và đồ uống
  • Chế tạo chất bán dẫn
  • Hệ thống điều khiển
Model tM-P8 tM-PDW8
Digital Input/Counter
Input Channels 8
Type Wet Contact (Sink, Source) Wet Contact (Sink, Source) + Dry Contact(Source)
Wet Contact ON Voltage Level +3.5 VDC ~ 50 VDC
OFF Voltage Level +1 VDC Max.
Dry Contact ON Voltage Level Close to GND
OFF Voltage Level Open
Counters Max. Count 65535 (16-bit)
Max. Input Frequency 100 Hz
Min. Pulse Width 5 ms
Input Impedance 10 KΩ, 0.5 W 
Overvoltage Protection ±70 VDC
Model tM-P8 tM-PDW8
Communication
Interface RS-485
Format (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1)
Baud Rate 1200 ~ 115200 bps
Protocol DCON, Modbus/RTU, Modbus/ASCII
Dual Watchdog Yes, Module (2.3 seconds), Communication (Programmable)
LED Indicators
Power 1 LED as Power Indicator
Isolation
Intra-module Isolation,Field-to-Logic 3750 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power
Power Requirements
Reverse Polarity Protection Yes
Powered from Terminal Block Yes, 10 ~ 30 VDC
Consumption 0.2 W Max. 0.43 W Max.
Mechanical
Dimensions (W x L x H) 52 mm x 98 mm x 27 mm
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +75 °C
Humidity 10 ~ 95% RH, Non-condensing
tM-P8     CR 8-channel Isolation DI (Wet) Module (RoHS)
tM-7561 CR Isolated USB to RS-485 Converter (RoHS)
tM-7520U CR Isolated RS-232 to RS-485 Converter (RoHS)
tM-7510U CR Isolated RS-485 Repeater (RoHS)
MDR-20-24 CR 24 W Single Output Industrial DIN Rail Power Supply (RoHS)
TOP HOME