Safety
Standard UL508, TUV EN60950-1 approved
EMC
Standard Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3, EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47, GL approved
Input
Voltage Range 88 ~ 264 VAC
124 ~ 370 VDC
Frequency Range 47 ~ 63Hz
AC Current (Typ.) 1.4 A/115 VAC
0.7 A/230 VAC
Inrush Current (Typ.) 35 A/115 VAC
70 A/230 VAC
Leakage Current <1 mA/240 VAC
Output
Ripple & Noise (Max.) 100mVp-p
Voltage Adj. Range 12 ~ 14V
Voltage Tolerance ±1.0%
Line Regulation ±0.5%
Load Regulation ±1.0%
Setup, Rise Time 1500ms, 60ms/230 VAC
3000ms, 60ms/115 VAC at full load
Hold Up Time (Typ.) 20ms/230 VAC
20ms/115 VAC at full load
DC Voltage 12 V
Rated Power 120 W
Rated Current 10 A
Efficiency 89%
Protection
Over Voltage 14 ~ 17V
Protection type : Shut down o/p voltage, re-power on to recover
Overload Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage
>150% rated power, constant current limiting with auto-recovery within 3 seconds and shut down o/p voltage after 3 seconds
Function
DC OK Active Signal (Max.) 60 VDC/0.3A, 30VDC/1A, 30VAC/0.5A resistive load
Mechanical
Casing Metal
Dimensions (mm) (63 * 125.2 * 113.5)mm
Environment
Over-temperature Protection 95°C ±5°C (TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
Temperature Coefficient ±0.03%/°C (0 ~ 50°C)
Operating Temperature -25 ~ +70°C (Refer to “Derating Curve”)
Storage Temperature -40 ~ +85°C
Humidity 20 ~ 95% RH Non-condensing