Trang chủ » IIoT » Bộ quản lý năng lượng điện tập trung màn hình cảm ứng 10 inch kết nối RS-232/485 + PoE Ethernet + App Line ICP DAS PMD-4201-TC

Bộ quản lý năng lượng điện tập trung màn hình cảm ứng 10 inch kết nối RS-232/485 + PoE Ethernet + App Line ICP DAS PMD-4201-TC

IIoT Power Meter Concentrator with 10.4″ Touch Panel

Chia sẻ:
Model: PMD-4201-TC
Views: 769

Bộ quản lý năng lượng điện tập trung màn hình cảm ứng 10 inch kết nối RS-232/485 + PoE Ethernet + App Line ICP DAS PMD-4201-TC

The PMD-4201 is a web-based intelligent Power Meter Concentrator developed by ICP DAS. It offers webpage interface, and features various functions such as: power data collection, logic control, power demand management, data logger, local display/Web page data display and alarm notification functions. PMD-4201 allows connections to ICP DAS Smart Power Meters via RS-485 or Ethernet interface to read the power data of the devices measured by the power meters; and then real-time record the power values in the data logger file. PMD-4201 also provides data logger file auto send-back function; together with PMC Data Server software or SCADA software, it allows collection and analysis of the power data. PMD-4201 is equipped with the 10.4″ TFT LCD (with Touch Panel) and designed for panel mount installation. It provides an easy way for viewing the power data and setting the system parameters at the local side. In addition, PMD-4201 also is equipped with built-in Web Server that allows direct connections via browsers to the PMD-4201 for viewing power data and setting up the system parameters. PMD-4201 also supports the Modbus TCP/RTU, SNMP, FTP and MQTT protocols for seamless integration with the back-end SCADA/MES/IT/IoT/Network Management systems. In addition to ICP DAS M-7000 I/O modules, the PMD-4201 could connect to standard Modbus TCP/RTU Slave modules. By working with the I/O modules, and functions such as IF-THEN-ELSE logic rule execution and alarm notification functions including LINE/Email, PMD-4201 offers more thought-out power demand management and alarm notification functions, and is able to perform load shedding of the devices if required, and enables real-time monitoring and control of the power consumption of the devices. When using PMD-4201 to build a power management and monitoring system, during the whole process of system development, no programming is required; it takes a few clicks on web page to complete all settings; it is easy for the user to quickly view the power data of the devices and furthermore process the data for statistics and analysis. The PMD-4201 is an easy-to-use and easy-to-build total solution for power management and monitoring that makes more efficient energy usage.

Energy measurement, monitoring and management

Software
Protocol • Modbus TCP/RTU for SCADA software
• FTP Client & Server
• SNMP & SNMP Trap
• MQTT Client (Message Publish & Subscribe; non-SSL & SSL)
• DDNS
Function • Web Interface & Local Display for Configuration
• IF-THEN-ELSE Logic operation (Unlimited rule supported)
• Power meters & I/O modules monitoring and control
• Data Logger operation
• Timer operation (Unlimited set supported)
• Schedule operation (More Powerful; Unlimited set supported)
• Internal Register operation (70 set supported)
• Instant message sending function (LINE Notify)
• non-SSL & SSL Email sending function
• SNTP Time Synchronization
Power Management • Power Data Display
• Historical Power Data Report
• Power Demand Management
• PUE Setting and Display
IoT Service Integration • ICP DAS IoTstar IoT Cloud Management Software
• Microsoft Azure IoT Cloud platform
• IBM Bluemix IoT Cloud platform
CPU Module
CPU 32-bit ARM CPU (1GHz)
Storage Expansion SD socket with 4 GB SD card (support up to 32 GB SD card)
Display
Size 10.4″ (4:3)
Backlight Life 50,000 hrs
Brightness 400 cd/m2
Resolution 800 x 600
Touch Panel 5-wire, resistive type; light transmission: 80 %
Contrast Ratio 20.834027777778
LED Indicators
Status 1 x Power
1 x Running
I/O Expansion
Remote Module Support M-7000/DL/IR Series Module
Modbus RTU Slave Module
Modbus TCP Slave Module
Power Meter PM Series Modbus meter
COM Ports
Ports COM 1: RS-485 (Data+, Data-); 2500 VDC isolated
COM 2: RS-485 (Data+, Data-); 2500 VDC isolated
COM 3: RS-485 (Data+, Data-, GND); 2500 VDC isolated
Ethernet
Ports RJ-45 x 1, 10/100/1000 Base-TX (LED indicators) (Auto-negotiating, Auto MDI/MDI-X)
Power
Input Range 12 ~ 48 VDC
Consumption 13 W
Powered from PoE Yes, IEEE 802.3af
Mechanical
Dimensions (mm) 291 x 229 x 54 (W x H x D)
Panel Cut-Out (mm) 277 x 215, ±1 (W x H)
Installation Panel Mounting, VESA (75 x 75) Mounting
Ingress Protection Rating Front panel: NEMA 4/IP65
Environment
Operating Temperature -10 ~ +60 °C
Storage Temperature -20 ~ +70 °C
Humidity 10 ~ 90% RH, Non-condensing
PMD-4201-TC     CR  IIoT Power Meter Concentrator with 10.4″ Touch Panel (Traditional Chinese) (RoHS)
TOP HOME