Views: 696

The PM-4324D series multi-circuit power meter monitors up to 8 three-phase circuits or 24 single-phase circuits, or any combination of single or three-phase circuits. The PM-4324D series can measure up to 24 currents via external Current Transformers (CTs). This flexibility makes the PM-4324D series perfect for multi-tenant facilities such as residential projects, office buildings and shopping malls. This compact instrument is designed to easily fit into existing panelboards or be flush mounted nearby, thus eliminating the need for expensive retrofit projects or for allocating extra space for the device. The digital temperature sensor function that provides one port for 2- or 3 wire DS18B20 digital temperature sensor input. This meter has LCD display shows power.

Model PM-4324D PM-4324D-MTCP PM-4324D-CPS
AC Power Measurement
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Measurement Voltage 10 ~ 600 V
Measurement Current CTO10 mm (60 A); CTO16 mm (100 A); CTO24 mm (200 A); CTO36 mm (300 A); CTO36 mm (400 A)
Measurement Frequency 50/60 Hz
W Accuracy Better than 0.5% (PF=1)
Power Parameter Measurement True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh),Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency
Data Update Rate 1 Second
LCD Display Yes
Communication
RS-485 Protocol Modbus RTU
Baud Rate 9600, 19200 (default), 38400, 115200; DIP Switch Selectable
Data Format N,8,1; N,8,2; E,8,1; E,8,2; O,8,1; O,8,2;
Isolation 3000 VDC
Ethernet Protocol Modbus TCP
Baud rate Protocol CANopen
Baud Rate 125 k (default), 250 k, 500 k, 1 M; DIP Switch Selectable
Isolation 3000 VDC
Alarm Output
Power Relay Form A (Normal Open) x 2; Relay Contact Voltage Range: 5 A @ 250 VAC (47 ~ 63 Hz), 5 A @ 30DC
Power
Input Range +85 ~ +264 VAC (277 VAC available)
Power Consumption 6 W
Mechanical
Casing Plastic
Dimensions (W x L x H) 237 mm x 57 mm x 134 mm
Module Installation DIN-Rail Mount
Environment
Operating Temperature -20 ~ +70 °C
Storage Temperature -25 ~ +80 °C
Ambient Relative Humidity 10% ~ 90% RH, Non-condensing
RS-485 Interface ~ Available soon ~
PM-4324DP CR Modbus RTU, Multi-Circuit Power Meter (Can be directly input from the secondary side of 333 mV CT) (RoHS)
PM-4324D-100P CR Modbus RTU, Multi-Circuit Power Meter; includes 60A CT (Inside diameter 10 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-160P CR Modbus RTU, Multi-Circuit Power Meter; includes 100A CT (Inside diameter 16 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-240P CR Modbus RTU, Multi-Circuit Power Meter; includes 200A CT (Inside diameter 24 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-360P CR Modbus RTU, Multi-Circuit Power Meter; includes 300A CT (Inside diameter 36 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-400P CR Modbus RTU, Multi-Circuit Power Meter; includes 400A CT (Inside diameter 36 mm; wire lead 4 m) x 24 (RoHS)
Ethernet Interface ~ Available soon ~
PM-4324D-100P-MTCP CR Modbus TCP, Multi-Circuit Power Meter; includes 60A CT (Inside diameter 10 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-160P-MTCP CR Modbus TCP, Multi-Circuit Power Meter; includes 100A CT (Inside diameter 16 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-240P-MTCP CR Modbus TCP, Multi-Circuit Power Meter; includes 200A CT (Inside diameter 24 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-360P-MTCP CR Modbus TCP, Multi-Circuit Power Meter; includes 300A CT (Inside diameter 36 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-400P-MTCP CR Modbus TCP, Multi-Circuit Power Meter; includes 400A CT (Inside diameter 36 mm; wire lead 4 m) x 24 (RoHS)
CAN bus Interface ~ Available soon ~
PM-4324D-100P-CPS CR CANopen, Multi-Circuit Power Meter; includes 60A CT (Inside diameter 10 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-160P-CPS CR CANopen, Multi-Circuit Power Meter; includes 100A CT (Inside diameter 16 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-240P-CPS CR CANopen, Multi-Circuit Power Meter; includes 200A CT (Inside diameter 24 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-360P-CPS CR CANopen, Multi-Circuit Power Meter; includes 300A CT (Inside diameter 36 mm; wire lead 4 m) x 24 (RoHS)
PM-4324D-400P-CPS CR CANopen, Multi-Circuit Power Meter; includes 400A CT (Inside diameter 36 mm; wire lead 4 m) x 24 (RoHS)