Trang chủ » Quản lý năng lượng thông minh » Bộ đo điện thông minh 3 pha bao gồm CT 60A kết nối CANopen ICP DAS PM-3133i-100P-CPS CR

Bộ đo điện thông minh 3 pha bao gồm CT 60A kết nối CANopen ICP DAS PM-3133i-100P-CPS CR

Isolated 3-phase Smart Power Meter

Chia sẻ:
Model: PM-3133i-100P-CPS CR
Views: 490

Bộ đo điện thông minh 3 pha bao gồm CT 60A kết nối CANopen ICP DAS PM-3133i-100P-CPS CR

ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-3133i series that gives you access to real-time electric usage for three-phase power measurement. With its high accuracy (<0.5%, PF=1 ), the PM-3133i series can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation. These compact size and cost-effective power meters are equipped with revolutionary wired clip-on CT (various types, support input current up to 400 A). It operates over a wide input voltages range 10 ~ 600 VAC which allows worldwide compatibility. Built-in AC isolator protection, this means total isolation between the AC measurement side and the control side.

• Generator monitoring
• Switchgear distribution systems
• Energy Management
• Power quality analysis

AC Power Measurement
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Loops Three-phase
Input Voltage 10 ~ 600 V; built-in isolation transformer
Input Current CTØ10 mm (0.05 A ~ 60 A)
Input Frequency 50 Hz (Range 45 ~ 55 Hz)/60 Hz (Range 55 ~ 65 Hz)
W Accuracy Better than 0.5% (PF=1)
Power Parameter Measurement True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency (45 ~ 65 Hz)
Data Update Rate 1 Second
CT
Includes CTs 3
Type Clip
Max. Current 60 A
Inside Diameter 10 mm
Leading Cable 4 m
CANopen
Baud Rate 125 k (default), 250 k, 500 k,
1 M; DIP Switch Selectable
Isolation 3000 VDC
Porotocol CANopen
Power
Input Range +12 ~ 48 VDC
Consumption 2 W
Mechanical
Casing Plastic
Dimensions (mm) 33 x 127 x 100 (W x L x H)
Installation DIN-Rail Mounting
Environmental
Operating Temperature -20 ~ +70 °C
Storage Temperature -25 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
PM-3133i-100P-CPS     CR CANopen, Isolated 3-phase power meter; includes 60A CT (Inside diameter 10 mm; wire lead 4 m) x 3 (RoHS)