Card PCI 1 cổng CAN ICP DAS PISO-CAN100U-T CR
- Product
- Solutions
- Company
- Support
- Contact Us
1-Port CAN Universal PCI Card
Tính năng
Card PCI 1 cổng CAN ICP DAS PISO-CAN100U-T CR
Note: We have verified to drive 100 CAN nodes at the same time via one CAN port of PISO-CAN100U.
Card PCI 1 cổng CAN ICP DAS PISO-CAN100U-T CR
In order to satisfy the users to apply the RTX system, ICPDAS provides the RTX driver for PISO-CAN series CAN card. If users want to combine the CAN communication interface in their time-critical system, the RTX driver of the PISO-CAN series CAN cards can help them to do this easily and quickly. Furthermore, the name and parameters of the APIs in the RTX driver are the same as in the Windows driver. Users don’t need to pay more efforts to study how to use the APIs of the RTX driver if they have used the Windows driver before. The RTX driver increases the additional worth of the PISO-CAN series CAN cards, and satisfies the users to get the highly real-time system. By owing to the feature of high price performance and highly real-time, PISO-CAN series CAN cards will be applied in more wide and more variant CAN applications.
Features:
Real-time Test:
The SocketCAN is based on the Linux operating system, and it contains the implementation interface of the network stack and the hardware driver. The hardware manufacturers program the hardware driver for the SocketCAN, and the network stack provides the standard BSD Socket APIs for users. Therefore, from the users’ point of view, they can easily and quickly program their applications without being familiar with the various APIs of the different hardware interface through the SocketCAN network stack.
We have provided the SocketCAN drivers for several kinds of CAN interface cards. Users can implement their SocketCAN-based application on the Linux platform by using these cards. Besides, we also support static library of CANopen/DeviceNet master on x86 hardware platform. It can help users communicate with CANopen/DeviceNet slaves more easily. Features:
Note:
|
ActiveX Tool
In order to use PISO-CAN200/400 easier, we provide a PISOCANX ActiveX component (OCX).
It is a useful element to develop the PISO-CAN200/400 application on different program development platform, and it also help users to reduce their development period.
Specially, users can use this in their SCADA softwares which support ActiveX technology. It would be possible to use SCADA software to control or monitor CAN devices. If users want to get PISOCANX, it will be found after installing the PISO-CAN200/400 driver with 1.16 version or later.
LabVIEW Tool
In order to apply the PISO-CAN200/400 to CAN network with NI LabVIEW, we provides a LabVIEW 7/7.1 toolkit for the purpose. It is a useful tool to develop the CAN-relative application in NI LabVIEW environment by using PISO-CAN200/400. It is easy to use and can help user to rapidly reduce their program development cycle. If users want to develop a LabVIEW industrial application with CAN network, the LabVIEW CAN driver is very helpful.
CAN LabVIEW Tool Features:
CAN LabVIEW Tool Features:
DASYLab Tool
In order to easy to use the PISO-CAN200/400 to CAN network for user. We provides a DASYLab version 8.0 toolkit for the purpose. It is a useful tool to develop the CAN-relative application in DASYLab environment by using PISO-CAN200/400. It can help user to rapidly reduce their program development cycle. If users want to develop a DASYLab industrial application with CAN network, the DASYLab CAN driver is very helpful.
CAN DASYLab Tool Features:
CANopen Tools
In order to apply the CANopen protocol on the PISO-CAN200/400 easily, we provides two CANopen application Tools, which are CANopen library and CANopen diagnosis application tool. If users want to develop an industrial application with CANopen protocol, the CANopen library is very helpful to be applied with the PISO-CAN200/400 as the CANopen devices with the features of CANopen protocol. Besides, if the monitor and diagnosis of CANopen message on the CAN network is considered, the CANopen diagnostic application tool can be used to achieve this purpose.
DeviceNet Tools
– DeviceNet is a low level network that provides connections between simple industrial devices (sensors, actuators) and higher level devices (controllers). It allows direct peer to peer data exchange between nodes in an organized and, if necessary, deterministic manner. We provides DeviceNet library for users to develop the specific DeviceNet application by PISO-CAN200/400. In addition, we also provide the DeviceNet diagnosis application tool to monitor and diagnose the DeviceNet message through CAN network. It provides the DeviceNet communication protocol interface to control and analysis the DeviceNet slaves.
DevcieNet Application Tool Features
DevcieNet Master X-Server Features
Linux kernel version of distributions
|
|
Linux kernel Distribution
|
2.6.37
|
Debian GUN/Linux
|
4.0
|
Fedora Core
|
2/3/4/5/6/7/8
|
Mandrake(Mandriva)
|
10.0/10.1/10.2
|
Red Hat Enterprise
|
4/5
|
Ubuntu
|
7.04
|
SUSE
|
9.1/9.2/9.3/10.0
|
Test development:
OS:Windows XP SP 3
CPU:Intel Core 2 Duo 2.00 GHz
RAM:512 MB
Baud Rate(bps)
|
CAN 2.0 A
|
CAN 2.0 B
|
Frame per sec.
|
Frame per sec.
|
|
1000 k
|
7493
|
6387
|
800 k
|
6185
|
5249
|
500 k
|
4088
|
3463
|
250 k
|
2134
|
1808
|
125 k
|
1096
|
924
|
50 k
|
438
|
370
|
20 k
|
175
|
148
|
10 k
|
88
|
74
|
Note:The test result is the average value of receiving 100000 CAN messages.
Model Name
|
PISO-CAN100U-D
|
PISO-CAN100U-T
|
Bus Interface
|
||
Type
|
Universal PCI, 3.3 V and 5 V, 33 MHz, 32-bit, plug and play
|
|
CAN Interface
|
||
Controller
|
NXP SJA1000T with 16 MHz clock
|
|
Transceiver
|
NXP 82C250
|
|
Channel number
|
1
|
|
Connector
|
9-pin male D-Sub
|
5-pin screwed terminal block
|
Baud Rate (bps)
|
10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, 1 M (allow user-defined baud rate)
|
|
Isolation
|
3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
|
|
Terminal Resistor
|
Jumper for 120 Ω terminal resistor
|
|
Power
|
||
Power Consumption
|
225 mA @ 5 V
|
|
Software
|
||
Driver
|
Windows XP/7/8/10 (32-bit/64-bit OS), Linux 2.6.x ~ 4.8.0, LabView, DASYLab, InduSoft
|
|
Library
|
VB 6.0, VC++ 6.0, BCB 6.0, Delphi 4.0, C#.Net, VB.Net
|
|
Mechanism
|
||
Dimensions
|
126mm x 22mm x 85mm (W x L x H)
|
|
Environment
|
||
Operating Temp.
|
-20 ~ +60℃
|
|
Storage Temp.
|
-40 ~ +70℃
|
|
Humidity
|
5 ~ 85% RH, non-condensing
|