Trang chủ » IIoT » Cảm biến phát hiện chuyển động (PIR)+nhiệt độ kết nối RS-485 Modbus RTU ICP DAS PIR-130-AC CR

Cảm biến phát hiện chuyển động (PIR)+nhiệt độ kết nối RS-485 Modbus RTU ICP DAS PIR-130-AC CR

PIR Motion Sensor (4m) and Temperature Sensor Module (AC powered)

Chia sẻ:
Model: PIR-130-AC CR
Views: 1370

Cảm biến phát hiện chuyển động (PIR)+nhiệt độ kết nối RS-485 Modbus RTU ICP DAS PIR-130-AC CR

The PIR-130 module includes a 1-channel passive infrared (PIR) sensor that is able to detect infrared waves generated by human within a range of approximately 8 meters in diameter with a 360° coverage area. The PIR-130 is used for indoor motion detection, and can be configured to automatically switch on a light if motion is detected. The PIR-130 module also includes a 1-channel temperature sensor that can be used for measuring room temperature or can be configured to activate a fire alarm.
  • Common toilets, for lights & exhaust fans
  • Common staircases
  • For parking lights
  • For garden lights
  • For changing rooms in shops
  • For corridors & many more
Model PIR-130-AC PIR-130-DC
PIR
Time-delay Hardware: 8-step Switch-selectable (seconds): 6, 16, 33, 66, 131, 262, 524, 1049
Software: 16-step (seconds): 2, 4, 6, 8, 16, 33, 49, 66, 131, 262, 393, 524, 1049, 2097, 3146, 4194
LUX Control Level Hardware: 2 mode (Dawn and dust) / Software: 5-step
Detection Range Distance: 4 meters Max.
Detection Field of View 360o; Diameter 8 meters Max.
Response Time 1 seconds
Temperature Sensor
Measurement Range -25 ~ +100°C
Fire Alarm 65°C (Programmable)
Resolution 0.0625°C
Accuracy ±2°C
Relay Output
Channels 1
Type Power Relay, Form C
Max. Load Current NO: 10 A @ 250 VAC
NC: 6 A @ 250 VAC
Load Wattage Incandescent Bulb: 1500 W Max.; Fluorescent Lamp 300 W Max.
RS-485 Interface
COM Port RS-485
Transmission Distance (m) Dependent on Baud Rate. For example, 1200 m Max. at 9600 bps.
Baud Rate (bps) 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Protocol DCON, Modbus RTU
Node Address Hardware: 160 ~ 191 / Software: 1 ~ 255
LED Indicators
LED Indicators Yes,1 as Power/Communication Indicator. 1 as Alarm Indicator.
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal, ±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power Line
Power Requirements
Power supply 110 ~ 220 VAC 10 ~ 30 VDC
Protection Power reverse polarity protection, Over-voltage brown-out protection
Power Consumption 2 W 1.3 W
Mechanical
Installation Ceiling mounting
Protection Class IP20
Dimensions (D x H) O 121 mm x 52 mm
Environment
Operating Temperature 0 to +35°C
Storage Temperature -30 ~ +80°C
Humidity 10 to 90% RH, Non-condensing
PIR-130-AC     CR PIR Motion Sensor (4m) and Temperature Sensor Module (RS-485) (110~220 VAC powered) (RoHS)
TOP HOME