Link youtube Link facebook
Trang chủ » Module 8 kênh đầu vào tương tự, 4 kênh đầu vào số, 4 kênh đầu ra số ICP DAS PET-7H16M

Module 8 kênh đầu vào tương tự, 4 kênh đầu vào số, 4 kênh đầu ra số ICP DAS PET-7H16M

Ethernet High Speed Data Acquisition Module with 8-channel 16-bit Simultaneously Sampled Analog Input, 4-channel Digital Input, 4-channel Digital Output

Model: PET-7H16M

datasheet manual
Views: 497
4.3 (85%) 4 votes
Chia sẻ:

Introduction

The PET-7H16M is an high speed data acquisition devices built-in a Ethernet communication port for data transfer over the network and it includes eight high speed 16-bit single-ended analog inputs (200 KHz sample and hold for 8 channels), 4-channel digital inputs and 4-channel digital outputs. It provides programmable input range on all analog channels (±5 V and ±10 V), digital output can be set output with Short-circuit protection and overload protection. PET-7H16M also has qualification for 4 kV ESD protection as well as 2500 VDC intra module isolation. In addition, the 16-bit ADC includes built-in anti-aliasing filtering to adjust the appropriate sampling rate and filter out modulator and signal noise. The PET-7H16M is not only suitable for a wide range of mobile/portable measurement applications, but also for precision signal measurement.

TOP HOME

Application

Factory Automation

Machine Automation

Remote Maintenance

Remote Diagnosis

Testing Equipment

TOP HOME

Features

1. Data transmission mode
1. Continuous transmission mode (Max. sampling rate of 30 kHz per channel)
2. N data samples mode (Max. sampling rate of 200 kHz per channel)

2. A/D trigger mode
1. Software AD Data Acquisition mode
2. External Digital Signal Event Trigger mode
3. External Clock AD Conversion Data Acquisition mode

3. External Digital Signal Event Trigger mode
1. Pre-Trigger (acquisition of N data samples)
2. Post-Trigger (acquisition of N data samples)

4. Software Support
1. VC, C#, VB.NET API and Demo
2. LabVIEW Toolkit and Demo

TOP HOME

TOP HOME

Specification

CPU
CPU 80186 , 80MHz
SRAM 512 KB
Flash Memory 512 KB
EEPROM 16 KB
Dual Watchdog Yes
Communication
Serial Port RS-232 (TXD, RXD, GND) (115200 bps Max.)
Ethernet Port 10/100 Base TX (With Link, Activity LED Indicator)
Small Man Machine Interface
7 Segment LED Display 5 Digits
System LED Indicator 4
Push Button 4
Digital Output
Output Channels 18
LED Indicator Yes
Output Type Power Relay, Form A (Normal Open)
Operating Voltage Range 5 ~ 240 VAC (47~63Hz)
5 ~ 24 VDC
Relay Contact Voltage Range 0 ~ 250 VAC (47~63 Hz)
0 ~ 28 VDC
Max. Load Current 5.0 A/Channel
Max. Operate Time 15 ms Max.
Max. Release Time 3 ms Max.
Insulation Resistance Min. 1,000 MOhms, at 500 VDC
Dielectric Strength Between Open Contacts : 750 VAC 50/60Hz (at 1 Minute)
Between Coil and Contacts : 4,000VAC 50/60Hz (at 1 Minute)
Surge Strength 10,000 V (at 1.2*50us)
Relay Life Mechanical :10 million operations at no Load Condition
Electrical : 100, 000, 28 VDC@5A min. , Resistive
Output Channels 6
LED Indicator Yes
Output Type Power Relay, Form C (Normal Open and Close)
Operating Voltage Range 5 ~ 240VAC (47~63Hz)
5 ~ 24VDC
Relay Contact Voltage Range 0~ 250VAC (47~63Hz)
0~ 30VDC
Max. load Current 2.0 A/Channel
Max. Operate Time 5 ms Max.
Max. Release Time 5 ms Max.
Insulation Resistance Min. 1,000 MOhms, at 500VDC
Dielectric Strength Between Open Contacts : 1,000Vrms (at 1 Minute)
Between Coil and Contacts : 1,500Vrms (at 1 Minute)
Surge Strength 2,500V (at 1.2*50us)
Relay Life Mechanical : 100 million operations at no Load Condition
Electrical : 100, 000, 30VDC@2A min. , Resistive
3 Way Isolation
Ethernet 1500V rms
I/O 3750V rms
Power 1000 VDC
Mounting
Din Rail Mount Yes
Wall Mount Yes
Power Requirements
Power Input +10 to +30 VDC
Power Consumption 3.0W
Environment
Environment Operating Temperature: –25 ~ +75 °C
Storage Temperature: –30 ~ +75 °C
Relative Humidity : 10 to 95% RH, non-condensing
Certification CE, FCC Detail
Dimensions
180mm x 111mm x 70mm (W x D x H)
TOP HOME

Ordering Information

ET2-6064D    24-channel Relay Output
ET2-6064D CR    24-channel Relay Output (RoHS)
TOP HOME