Trang chủ » Accessories » Bộ đổi nguồn DIN 220VAC/48VDC 1.25A ICP DAS MDR-60-48

Bộ đổi nguồn DIN 220VAC/48VDC 1.25A ICP DAS MDR-60-48

60W Single Output Industrial DIN Rail Power Supply

Chia sẻ:
Model: MDR-60-48
Views: 482

Bộ đổi nguồn DIN 220VAC/48VDC 1.25A ICP DAS MDR-60-48

Input
Voltage range 85 ~ 264 VAC
120 ~ 370 VDC
Frequency range 47 ~ 63 Hz
Efficiency (Typ.) 87%
Leakage current (max.) 1.8 A/115 VAC
1 A/230 VAC
Inrush Current (Typ.) COLD START 30 A/115 VAC
60 A/230 VAC
Leakage current <1 mA / 240 VAC
Output
DC Voltage 48 V
Rated Current 1.25 A
Current Range 0 ~ 1.25 A
Rated power 60 W
Ripple & noise (max.)   Note.2 200mVp-p
Voltage ADJ. range 48 ~ 56 V
Voltage Tolerance       Note.3 ±1.0%
Line Regulation ±1.0%
Load regulation ±1.0%
Setup, rise Time         Note.5 500 ms, 30 ms/230 VAC
500 ms, 30 m/115 VAC at full load
Hold up time (Typ.) 50 ms/230 VAC
20 ms/115 VAC at full load
Protection
Overload 105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Over voltage 57.6 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
Function
DC OK signal Relay contact rating(max.): 30V/1A resistive
Environmental
Working temp. -20 ~ +70°C (Refer to output load derating curve)
Working humidity 20 ~ 90% RH non-condensing
Storage TEMP., humidity -40 ~ +85°C , 10 ~ 95% RH
TEMP. Coefficient ±0.03%/°C (0 ~ 50°C)
Vibration Component : each along X, Y, Z axes ;
Mounting : Compliance to IEC60068-2-6 10 ~ 500Hz, 2G 10min./1cycle, period for 60min.
Safety & EMC (Note 4)
Safety standards UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only)
Withstand voltage I/P-O/P:3KVAC      I/P-FG:1.5KVAC      O/P-FG:0.5KVAC
Isolation resistance I/P-O/P, I/P-FG, O/P-FG:>100M Ohms/500VDC 25°C 70%RH
EMI Conduction & Radiation Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B
Hsrmonic current Compliance to EN61000-3-2,-3
EMS immunity Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
DC OK Relay Contact
Contact Close When the output voltage reaches the adjusted output voltage.
Contact Open When the output voltage drop below 90% output voltage.
Contact Ratings (max.) 30V/1A resistive load
Others
MTBF 299.2K hrs min.
MIL-HDBK-217F (25°C)
Dimension (W x H x D) 40 mm x 90 mm x 100 mm
Packing 0.33Kg; 42pcs/14.8Kg/0.82CUFT
NOTE
  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
  5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time

 

Safety
Standard UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only)
EMC
Standard Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3,
EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
Input
Voltage Range 85 ~ 264 VAC
120 ~ 370 VDC
Frequency Range 47 ~ 63 Hz
Inrush Current (Typ.) COLD START 30 A/115 VAC
60 A/230 VAC
Leakage Current <1 mA / 240 VAC
Output
Ripple & Noise (Max.) 200mVp-p
Voltage Adj. Range 48 ~ 56 V
Voltage Tolerance ±1.0%
Line Regulation ±1.0%
Load Regulation ±1.0%
Setup, Rise Time 500 ms, 30 ms/230 VAC
500 ms, 30 m/115 VAC at full load
Hold Up Time (Typ.) 50 ms/230 VAC
20 ms/115 VAC at full load
DC Voltage 48 V
Rated Power 60 W
Rated Current 1.25 A
Efficiency 87%
Protection
Over Voltage 57.6 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
Overload 105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Function
DC OK Active Signal (Max.) 30V/1A resistive
Mechanical
Casing Plastic
Dimensions (mm) (40 * 90 * 100) mm
Environment
Operating Temperature -20 ~ +70 °C
Storage Temperature -40 ~ +85°C
Humidity 20 ~ 90% RH Non-condensing
MDR-60-48 CR 48V/1.25A, 60W Single Output Industrial DIN Rail Power Supply