Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module RS-485 Modbus RTU 7 kênh đầu ra Photo-Mos Relay ICP DAS M-7066PD-G CR

Module RS-485 Modbus RTU 7 kênh đầu ra Photo-Mos Relay ICP DAS M-7066PD-G CR

7-ch PhotoMos Relay (1 A @ 80 V) Module with LED Display

Chia sẻ:
Model: M-7066PD-G CR
Views: 328

Module RS-485 Modbus RTU 7 kênh đầu ra Photo-Mos Relay ICP DAS M-7066PD-G CR

Both the I-7066 and the M-7066P feature seven Form A PhotoMOS relay output channels. In comparison to electromechanical relays, the PhotoMOS relays provide a faster response time, greater electrical endurance, higher vibration and shock resistance. There are also no arcing, no bounce, and no switching noise for the PhotoMOS relay. There are options for configuring power-on and safe digital output values, and both the I-7066D and the M-7066PD each include seven LED indicators that are used to display channel status as well as providing 4 kV ESD protection.

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Display
Type I/O LED Indicator
Isolation
Intra-module Isolation 2000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for 8 Relay and Power Line
±2 kV for RS-485 Port Line
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Line
LED Indicators
Status 1 x Power and Communication
7 x Relay Output
Relay Output
Channels 7 (Form A)
Type PhotoMOS Relay
Contact Rating Form A:
80 V (AC peck or DC) @ 1 A
0.24 A @ 220 VDC
0.25 A @ 250 VAC
Leakage Current 1 uA
Operate Time 5 ms (Max.)
Release Time 0.2 ms (Max.)
Electrical Endurance Long Life, And No Arcing, No Bounce, And No Switching Noise
Power on Value Yes, Programmable
Safe Value Yes, Programmable
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol Modbus RTU, DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 0.9 W
Mechanical
Dimensions (mm) 123 x 72 x 35 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
M-7066PD-G     CR 7-ch PhotoMos Relay (1 A @ 80 V) Module with LED Display using DCON and Modbus Protocols (Gray Cover) (RoHS)

 