Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module RS-485 Modbus RTU 4 kênh đầu vào số (DI)+4 kênh đầu ra Relay ICP DAS M-7060-G CR

Module RS-485 Modbus RTU 4 kênh đầu vào số (DI)+4 kênh đầu ra Relay ICP DAS M-7060-G CR

4-ch Isolated DI (Wet, 4~30 VDC) and 4-ch Signal Relay Module

Chia sẻ:
Model: M-7060-G CR
Views: 460

Module RS-485 Modbus RTU 4 kênh đầu vào số (DI)+4 kênh đầu ra Relay ICP DAS M-7060-G CR

The 7060 series provides 4 digital input channels, 2 Form A and 2 Form C signal relay output channels, while the M-7060P provides 4 digital input channels, 2 Form A and 2 Form C power relay output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. The “D” versions of the 7060 series provide eight LED indicators that can be used to monitor the status of the digital input and relay output. The “M” versions of the 7060 series support both the Modbus RTU and DCON protocols, which can be configured via software. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments. The 7060 series is the ideal solution for small signal switching applications, while the M-7060P is the perfect solution for high power applications.

  • Tự động hóa tòa nhà
  • Tự động hóa nhà máy
  • Máy tự động
  • Bảo trì từ xa
  • Chẩn đoán từ xa
  • Kiểm tra trang thiết bị

 

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Isolation
Intra-module Isolation 3750 VDC
EMS Protection
EFT (IEC 61000-4-4) ±2 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Point
LED Indicators
Status 1 x Power and Communication
Digital Input/Counter
Channels 4
Type Wet Contact
Sink/Source (NPN/PNP) Sink/Source
ON Voltage Level +1 VDC Max.
OFF Voltage Level +4 ~ 30 VDC
Max. Counts 65535 (16-bit)
Frequency 100 Hz
Min. Pulse Width 5 ms
Input Impedance 3 kΩ
Overvoltage Protection ±35 VDC
Relay Output
Channels 4 (2 x Form, 2 x Form C)
Type Signal Relay
Contact Material Gold-plated silver
Contact Rating Form A:
0.6 A @ 125 VAC
2 A @ 30 VDC
Form C:
0.6 A @ 125 VAC
2 A @ 30 VDC
Operate Time 3 ms
Release Time 2 ms
Electrical Endurance 5 x 10^5 ops.
Mechanical Endurance 1 x 10^8 ops.
Surge Strength 1500 VDC
Power on Value Yes
Safe Value Yes
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), (O, 8, 1)
Protocol Modbus RTU, DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 1 W
Mechanical
Dimensions (mm) 123 x 72 x 35 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
M-7060-G     CR 4-ch Isolated DI (Wet, 4~30 VDC) and 4-ch Signal Relay Module using DCON and Modbus Protocols (Gray Cover) (RoHS)