Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module RS-485 Modbus RTU 4 kênh đầu ra tương tự 16-bit +4 kênh DI+ 4 kênh DO ICP DAS M-7024UD-G CR

Module RS-485 Modbus RTU 4 kênh đầu ra tương tự 16-bit +4 kênh DI+ 4 kênh DO ICP DAS M-7024UD-G CR

4-ch 16-bit AO Module with 4 DI, 4 DO and LED Display

Chia sẻ:
Model: M-7024UD-G CR
Views: 538

Module RS-485 Modbus RTU 4 kênh đầu ra tương tự 16-bit +4 kênh DI+ 4 kênh DO ICP DAS M-7024UD-G CR

The M-7024U is a multi-function module that includes 4 analog output channels, 4 digital input channels, 4 digital output channels. It provides a programmable output range on all analog outputs channels (0 ~ 5 V, +/-5 V, 0 ~ 10 V, +/-10 V, +4 ~ +20 mA or 0 ~ +20 mA). Each analog output channel can be configured for an individual range and the module also features per-channel open wire detection for +4 ~ +20 mA outputs, together with 8 kV ESD Protection as well as 2500 VDC intra-module isolation. Options for configuring power-on and safe values are also included.

• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Display
Type I/O LED Indicator
Isolation
Intra-module Isolation 2500 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±8 kV Contact for each Terminal
LED Indicators
Status 1 x Power and Communication
4 x Analog Input
4 x Digital Input
4 x Digital Output
Analog Output
Channels 4
Type Voltage
Current
Range 0 ~+5 VDC, ±5 VDC, 0 ~ +10 VDC, ±10 VDC, 0 ~ +20 mA, +4 ~ +20 mA
Resolution 16-bit
Accuracy ±0.02%% of FSR
Short Circuit Protection Yes
DA Output Response Time 10 ms per channel
Programmable Output Slope Voltage: 0.0625 ~ 512 V/Second
Current: 0.125 ~ 1024 mA/Second
Current Output Wiring Source
Open Wire Detection Yes, for 4 ~ 20 mA only
Current Load Resistance 1000 Ω
Power on Value Yes, Programmable
Safe Value Yes, Programmable
Digital Input/Counter
Channels 4
Type Dry Contact
Wet Contact
Wet Contact, ON Voltage Level +1 VDC Max.
Wet Contact, OFF Voltage Level +4 ~ 30 VDC
Dry Contact, ON Voltage Level Close to GND
Dry Contact, OFF Voltage Level Open
Dry Contact, Effective Distance 500 M Max.
Max. Counts 16-bit (65535)
Frequency 100 Hz
Min. Pulse Width 5 ms
Overvoltage Protection +60 VDC
Digital Output
Channels 4
Type Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +3.5 VDC ~ +50 VDC
Max. Load Current 700 mA/Channel
Overvoltage Protection 60 VDC
Overload Protection 1.4 A (with short-circuit protection)
Short-Circuit Protection Yes
Power on Value Yes, Programmable
Safe Value Yes, Programmable
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol Modbus RTU, DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 4.5 W
Mechanical
Dimensions (mm) 123 x 72 x 35 (W x L x H)
Installation DIN-Rail
Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
M-7024UD-G     CR 4-ch 16-bit AO Module with 4 DI, 4 DO and LED Display using DCON and Modbus Protocols (Gray Cover) (RoHS)
TOP HOME