Trang chủ » Remote I/O Module and Unit » Module RS-485 DCON & Modbus RTU 2 kênh đầu ra tương tự (AO) ICP DAS M-7022-G CR

Module RS-485 DCON & Modbus RTU 2 kênh đầu ra tương tự (AO) ICP DAS M-7022-G CR

2-ch 12-bit AO Module with Channel-to-ch Isolation
Chia sẻ:
Model: M-7022-G CR
Views: 663

Module RS-485 DCON & Modbus RTU 2 kênh đầu ra tương tự (AO) ICP DAS M-7022-G CR

The I-7022 is a 12-bit, 2-channel Analog Output module that is designed for both voltage and current output using the DCON protocol. The I-7022 features 3000 VDC intra-module isolation, and the power source for the current output can be selected as either internal or external via a jumper. Options are also provided to allow power-on and safe values to be set. The M-7022 supports both the Modbus RTU and the DCON protocols which can be configured via software, and all hardware specifications are the same as the I-7022.
  • Tự động hóa tòa nhà
  • Tự động hóa nhà máy
  • Máy tự động
  • Bảo trì từ xa
  • Chẩn đoán từ xa
  • Kiểm tra trang thiết bị
Models I-7022 M-7022
Analog Output
Channels 2
Range Voltage 0 ~ +5 V, 0 ~ +10 V,
Current 0 ~ +20 mA, +4 ~ +20 mA
Resolution 12-bit
Accuracy 0.1%
Readback Accuracy ±0.5% of FSR
DA Output Response Time 10 ms
Programmable Output Slope Voltage 0.0625 ~ 1024.0 V/Second
Current 0.125 ~ 2048 mA/Second
Current Load Resistance Internal Power: 500 Ω
External Power: 1050 Ω
Open Wire Detection (for current only) Yes
Channel-to-Channel Isolation Yes, 2 kV
Short Circuit Protection Yes
Power-on Value Yes
Safe Value Yes
Models I-7022 M-7022
Communication
Interface RS-485
RS-485 Bias Resistor No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate 1200 to 115200 bps
Protocol DCON Modbus RTU, DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator Yes, 1 as Power/Communication Indicator
I/O LED Indicator
7-Segment LED Display
Isolation
Intra-Module Isolation, Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
EFT (IEC 61000-4-4) ±4 kV to Power Line
Surge (IEC 61000-4-5) ±0.5 kV for Power Line
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 3.0 W
Mechanical
Dimensions (L x W x H) 123 mm x 72 mm x 35 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 to +75°C
Storage Temperature -40 to +85°C
Humidity 10 to 95% RH, Non-condensing
M-7022-G     CR 2-ch 12-bit AO Module with Channel-to-ch Isolation using DCON and Modbus Protocols (Gray Cover) (RoHS)
tM-7520U CR RS-232 to RS-485 converter (RoHS)
tM-7561 CR USB to RS-485 converter (RoHS)
tM-SG4 CR RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS)
I-7514U CR 4-channel RS-485 Hub (RoHS)
SG-770 CR 7 channel differential or 14 channel single-ended surge protector (RoHS)
SG-3000 Series Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers