Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module RS-485 Modbus RTU 16 kênh đầu vào tương tự ICP DAS M-7018-16-G CR

Module RS-485 Modbus RTU 16 kênh đầu vào tương tự ICP DAS M-7018-16-G CR

16-ch Thermocouple Input Module

Chia sẻ:
Model: M-7018-16-G CR
Views: 800

Module RS-485 Modbus RTU 16 kênh đầu vào tương tự ICP DAS M-7018-16-G CR

The M-7018-16 is an analog input module that includes 16 differential analog input channels. The voltage input range can be from ±15 mV to ±2.5 V, the current input range can be either +4 to +20 mA, 0 to +20 mA, or ±20 mA, and types J, K, T, E, R, S, B, N, C, L, M, LDIN43710 thermocouple can be used for the thermocouple input. Overvoltage protection of up to 30 VDC is provided. The module also features per-channel open wire detection for the thermocouple input types, and provides 4 kV ESD protection as well as 3000 VDC intra-module isolation.

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Isolation
Intra-module Isolation 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV to Power
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
Surge (IEC 61000-4-5) ±2 kV for Power Line
LED Indicators
Status 1 x Power and Communication
Analog Input
Channels 16 Differential
Type Voltage
Current
Thermocouple
Sensor Type Thermocouple: J, K, T, E, R, S, B, N, C
Range Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
Current: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 Ω resistor)
Resolution 16-bit
Accuracy ±0.1% of FSR
Sampling Rate 10 Hz (Total)
Input Impedance > 400 kΩ
Common Voltage Protection 25 VDC
Overvoltage Protection ±30 VDC
Individual Channel Configuration
Open Wire Detection Yes
COM Ports
Ports 1 x RS-485
Baud Rate 1200 to 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol Modbus RTU, DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 0.5 W
Mechanical
Dimensions (mm) 120 x 76 x 42 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
M-7018-16-G     CR 16-ch Thermocouple Input Module using DCON and Modbus Protocols (Gray Cover) (RoHS)