Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module RS-485 Modbus RTU 2 kênh đầu vào 4-Wire Full-Bridge Strain Gauge+4 DO+1 DO ICP DAS M-7016D-G CR

Module RS-485 Modbus RTU 2 kênh đầu vào 4-Wire Full-Bridge Strain Gauge+4 DO+1 DO ICP DAS M-7016D-G CR

2-ch 4-wire Strain Gauge Input Module with LED Display

Chia sẻ:
Model: M-7016D-G CR
Views: 992

Module RS-485 Modbus RTU 2 kênh đầu vào 4-Wire Full-Bridge Strain Gauge+4 DO+1 DO ICP DAS M-7016D-G CR

In the industrial environment, there are numerous examples where force needs to be converted into a measurable electrical output. In most cases, a strain gauge or a load cell can be used. But the question is, how do we then deal with these electrical output measurements? In this situation, the I-7016 is definitely the No. 1 choice. Not only can the module process data from a load cell or a strain gauge, it also features linear mapping that can be used to directly convert the resulting data into weight via a user-defined correspondent table. The I-7016 supports full-bridge strain gauges and provides 2 Analog Input channels, 1 excitation voltage output channel, 1 Digital Input channels and 4 Digital Output channels. The module provides a programmable input range (±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, and ±2.5 V) and each Analog Input channel can be individually configured. Excitation voltage output can be in the range of 0 ~ +10 V, with a 40 mA driving efficiency. Digital Output channels can also be set as high or low alarm outputs. The M-7016 supports both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7016.
  • Tự động hóa tòa nhà
  • Tự động hóa nhà máy
  • Máy tự động
  • Bảo trì từ xa
  • Chẩn đoán từ xa
  • Kiểm tra trang thiết bị
CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Display
Type 5-Digit 7 Segment LED Display
Isolation
Intra-module Isolation 1500 VDC
LED Indicators
Status 1 x Power and Communication
Digital Input/Counter
Channels 1
Type Dry Contact
Sink/Source (NPN/PNP) Source
ON Voltage Level Close to GND
OFF Voltage Level Open
Max. Counts 16-bit
Frequency 50 Hz
Input Impedance 3 kΩ
Overvoltage Protection ±30 VDC
Digital Output
Channels 4
Type Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +3.5 ~ +50 VDC
Load Current 30 mA/Channel
Power on Value Yes
Safe Value Yes
Strain Gauge, Load Cell Input
Channels 2
Type Strain Gauge
Wiring Full-Bridge
Accuracy ±0.05% of FSR
Resolution 16-bit
Sampling Rate 10 Hz for 1-channel mode or 2 Hz (total) for 2-channel mode
Impedance 20 MΩ
Overvoltage Protection ±5 VDC
Excitation Voltage Output
Channels 1
Range 0 ~ +10 V
Resolution 16-bit
Accuracy ±0.05%
Max. Load Current 40 mA
Power on Value Yes
COM Ports
Ports 1 x RS-485
Baud Rate 1200 to 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol Modbus RTU, DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 3.0 W
Mechanical
Dimensions (mm) 123 x 72 x 35 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
M-7016D-G     CR 2-ch 4-wire Strain Gauge Input Module with LED Display using DCON and Modbus Protocols (Gray Cover) (RoHS)