Module điều khiển chiếu sáng 1 kênh Relay + 1 kênh DI AC ICP DAS LC-101H-E CR

Network type single loop light control module with AC load current measurement

Chia sẻ:
Model: LC-101H-E CR
Views: 1114

LC-101H-E and LC-102H-E are light control module designed for smart home applications. With the former being a single-loop and the latter a dual-loop model, both equipped with AC load current measurement capabilities. These modules not only effectively control lighting control loop, but also monitors the load current in real time, providing users with an intuitive understanding of the operating status of the lighting fixtures. Since the lamps used in a lighting circuit are usually inductive loads, switching them on and off generates a strong transient current (about 10 to 20 times the operating current), which may damage the relay in the module. The LC-101H-E and LC-102H-E are equipped with an Inrush Current-resistant high-power relay to withstand this transient current, prolonging the service life of the module and reducing the need for maintenance.
When the user turns on or off the lamp, the module can detect the switching status of the relay by measuring the load current, which ensures the normal operation of the lighting control system and timely detection of problems. In addition, the Form C design of the module’s lighting circuit relay supports double-cut circuit configuration of the physical switch, providing users with greater flexibility and convenience. In addition, the current measurement function helps users to monitor the load current and check the switching status of the relay to ensure the load works properly in the lighting circuit and prevent the relay from jamming.

The LC series lighting control modules are easy to use, requiring no specialised skills to install and operate, and no software to control the lighting channels. When software control is required, it can be programmed by Modbus TCP, Modbus UDP, MQTT, SNMP V2c communication protocols, and the communication address can be set by the hardware.

LC-10xH comparison table:

LC-101H-E LC-102H-E LC-101H LC-102H LC-103H
Communications Ethernet RS-485
Digital Input 1 2 1 2 1
Relay Output 1 2 1 2 3
Max. Load Current 30 A
(Resistive Load, recommend working current is 1.0 A with 220VAC)
16 A
(Resistive Load, recommend working current is 1.5 A with 220VAC)
Max. Lighting Loads (1) Incandescent Lamp: 6 units
(2) LED(Electronic ballast): 8 units
(1) Incandescent Lamp: 8 units
(2) LED(Electronic ballast): 10 units
Load Current Readback Yes No
AC Load Current Measurement  0 ~ 5 A No
Function Local and Remote Direct Control Relay ON/OFF and Remote Status Monitoring

Software
Function Built-in Web Server
CPU Module
CPU 32-bit ARM
Watchdog Timer Module Communication (Programmable)
Isolation
Intra-module Isolation 2-way Isolation
I/O: 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
LED Indicators
Status Power, Link, PoE
Digital Input
Channels LC-101H-E: 1
LC-102H-E: 2
Type Wet Contact, 90 ~ 240 VAC
ON Voltage Level 65 VAC
OFF Voltage Level 56 VAC
Isolation 3000 VDC
Input Impedance 68 KΩ, 2W
Relay Output
Channels LC-101H-E: 1
LC-102H-E: 2
Type Power Relay, Form C (SPDT N.O+N.C..)
Contact Rating 30 A @ 250 VAC
AC Load Current Measurement Yes, 0 ~ 5 A range with 3% of FSR Accuracy
Operate Time 15 ms Max
Release Time 22 ms Max.
Electrical Endurance 100,000 ops.
Mechanical Endurance 10,000,000 ops
Power on Value Yes
Safe Value Yes
Application Specification (1) Incandescent Lamp: 40W/ 220 VAC * 5 units
(2) LED(Electronic ballast): 40W/ 220 VAC *8 units
Ethernet
Ports 1 x RJ-45, 10/100 Base-Tx
PoE Yes
Access Control Password and IP Filter
Protocol Modbus TCP, Modbus UDP, MQTT, SNMP V2c
Power
Reverse Polarity Protection Yes
Consumption LC-101H-E: 1.9 W Max
LC-102H-E: 2.8 W Max
Powered from PoE IEEE 802.3af, Class1
Powered from Terminal Block +10 ~ +30 VDC
Mechanical
Dimensions (mm) 72 x 95 x 57 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +85°C
Humidity 10 ~ 90% RH, Non-condensing
LC-101H-E     CR  Network type single loop light control module with AC load current measurement
(1 Relay output with 1 AC AI + 1 AC DI) (RoHS)