The I-97024U is source type analog output modules, which offer 4 single-ended analog output channels. Every channel can be programmed to an individual output range of 0 ~ 5 V, ±5 V, 0 ~ 10 V, ±10 V, +4 ~ +20 mA or 0 ~ +20 mA. Open wire detection is provided for +4 ~ +20 mA output. Options for configuring power-on and safe values are also included. The I-97024U provide RF immunity level matching that defined by IEC 61000-4-3 standard, together with 4 kV ESD protection as well as 3000 VDC intra-module isolation
  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
Model I-97024U I-97028U
Analog Output
Channels 4 8
Current Output Wiring Source
Range 0 ~ +5 VDC, ±5 VDC, 0 ~ +10 VDC, ±10 VDC, 0 ~ +20 mA, +4 ~ +20 mA
Resolution 16-bit
Accuracy ±0.02% of FSR
Zero Drift ±0.2 μV/°C
Span Drift ±25 ppm/°C
DA Output Response Time 10 ms per channel
Programmable
Output Slope
Voltage 0.0625 ~ 512 V/Second
Current 0.125 ~ 1024 mA/Second
Output Capacity 1000 Ω
Open Wire Detection Yes, +4 ~ +20 mA
Short Circuit Protection Yes
Power-on Value Yes
Safe Value Yes
External Power Requirements
Reverse Polarity Protection Yes
Powered from Terminal Block Yes, 15 ~ 30 VDC
Consumption 4 W 7 W
Model I-97024U I-97028U
Communication
Interface RS-485
Format N, 8, 1
Baud Rate 1200 ~ 115200 bps
Protocol DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Display
System LED Indictors Yes, 1 as Power
I/O LED Indicators 8 LEDs as Analog Output Fault Indications 16 LEDs as Analog Output Fault Indications
Isolation
Intra-module Isolation, Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Point
RS Immunity (IEC 61000-4-3) 3 V/m, 80 MHz ~ 1 GHz
Power
Power Consumption 0.3 W Max.
Mechanical
Dimensions (L x W x H) 144 mm x 30.3 mm x 134 mm
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +85°C
Humidity 10 ~ 90% RH, non-condensing
I-97024U     CR 4-ch Isolated Analog Output Module (RoHS)