• Industrial Automation
• Industrial Machinery
• Building Automation
• Food and Beverage Systems
• Semiconductor Fabrication
• Control Systems
CPU Module |
Watchdog Timer |
Yes, Module (1.6 Seconds), Communication (Programmable) |
Isolation |
Intra-module Isolation |
3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for Each Terminal
±8 kV Air for Random Point |
RS Immunity (IEC 61000-4-3) |
±4 kV for Power |
LED Indicators |
Status |
1 x Power and Communication |
Analog Input |
Channels |
10 Differential or 20 Single-ended (See Note 1), Jumper selectable |
Range |
±150 mV, ±500 mV, ±1 VDC, ±5 VDC, ±10 VDC, ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (jumper selectable) |
Resolution |
16-bit |
Accuracy |
Normal Mode: ±0.1% of FSR
Fast Mode: ±0.5% of FSR |
Sampling Rate |
Normal Mode: 10 Hz (Total)
Fast Mode: 50 Hz (Total) |
Bandwidth |
Normal Mode: 15.7 Hz
Fast Mode: 78.7 Hz |
Input Impedance |
Voltage: 2 MΩ(Differential), 1 MΩ (Single-ended)
Current: 125 Ω |
Common Mode Rejection |
86 dB |
Normal Mode Rejection |
100 dB |
Overvoltage Protection |
Differential: 240 Vrms
Single-ended: 150 Vrms |
Overcurrent Protection |
50 mA Max. at 110 VDC/VAC Max. |
Individual Channel Configuration |
Yes |
Zero Drift |
±20 μV/°C |
Span Drift |
±25 ppm/°C |
COM Ports |
Ports |
1 x RS-485 |
Baud Rate |
1200 to 115200 bps |
Data Format |
N, 8, 1 |
Protocol |
DCON |
Power |
Consumption |
0.5 W Max. |
Mechanical |
Dimensions (mm) |
31 x 134 x 144 (W x L x H) |
Environment |
Operating Temperature |
-25 ~ +75 °C |
Storage Temperature |
-40 ~ +85 °C |
Humidity |
10 ~ 90% RH, Non-condensing |
Specification Memo
Note 1: Differential mode can be used for either voltage input or current input. Single-Ended mode can only be used for voltage input.