Module 2 kênh đầu vào bộ đếm/tần số RS-485 ICP DAS I-87082W-G CR

2-channel Counter/Frequency Input Module

Chia sẻ:
Model: I-87082W-G CR
Views: 1078

Module 2 kênh đầu vào bộ đếm/tần số RS-485 ICP DAS I-87082W-G CR

The I-87082W offers 2 high speed counter or frequency input channels and 2 digital output channels. Two types of digital input are provided, one for isolated input, and the other is for nonisolated input. The isolated input provides 3750 Vrms isolation voltage and the non-isolated input provides programmable threshold voltage level. The built-in digital filter is valid for both non-isolated and isolated input and can filter out noise where the high/low pulse width is smaller than the minimum high/low width of the digital filter. The maximum count is up to 32-bit and the maximum frequency is up to 100 kHz. The module also provides programmable alarm output with non-isolated open collectors.

• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Isolation
Intra-module Isolation 3750 Vrms
EMS Protection
ESD (IEC 61000-4-2) ± 4 kV Contact for Each Terminal
±8 kV Air for Random Point
LED Indicators
Status 1 x Power and Communication
8 x I/O
Digital Output
Channels 2
Sink/Source (NPN/PNP) Sink, Open Collector
Load Voltage +5 VDC ~ +30 VDC
Load Current 30 mA
Counter/Frequency/Encoder Input
Channels 2
Type Counter or Frequency
Counter/Encoder Bits 32-bits (4,294,967,295)
ON Voltage Level Isolated: +3.5 VDC ~ +30 VDC
Non-isolated: 0 ~ +5 VDC (Default > 2.4 VDC, Programmable)
OFF Voltage Level Isolated: +1 VDC Max.
Non-isolated: 0 ~ +5 VDC (Default < 0.8 VDC, Programmable)
Max. Counter/Frequency 100 kHz
Frequency Accuracy 1 Hz or 10 Hz (software selectable)
Programmable Alarm Mode Mode 0: High Alarm Comparator on Counter 0 and Counter 1
Mode 1: Two Steps High Alarm Comparator on Counter 1
Counter Mode Up
Low Pass Filter 2 ~ 65000 μs
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format N, 8, 1
Protocol DCON
Power
Consumption 0.5 W Max.
Mechanical
Dimensions (mm) 30 x 102 x 115 (W x L x H)
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
I-87082W-G     CR 2-ch Counter/Frequency Input Module (RoHS)