Trang chủ » Truyền thông công nghiệp » Bộ chuyển đổi RS-232 sang CAN ICP DAS I-7530T-G CR

Bộ chuyển đổi RS-232 sang CAN ICP DAS I-7530T-G CR

RS-232 to CAN Converter

Chia sẻ:
Model: I-7530T-G CR
Views: 1398

Bộ chuyển đổi RS-232 sang CAN ICP DAS I-7530T-G CR

CAN (Controller Area Network) is a serial bus system especially suited to structure intelligent industry devices networks and build smart automatic control systems. The following figure shows the application architecture for I-7530/I-7530T/I-7530FT modules. The PC can be the CAN host, monitor or HMI to access/control the CAN device through the CAN network by the I-7530/I-7530T/I-7530FT Converters. The programmable RS-232 device (For example: I-8411/I-8431/I-8811/I-8831/W-8031/W-8331/W-8731 embedded controller) can use the serial port to connect to the CAN network via the I-7530/I-7530T/I-7530FT modules. In order to use the CAN network with traditional RS-232 devices, we provide a way to achieve this purpose. The I-7530/I-7530T/I-7530FT are designed to unleash the power of CAN bus via RS-232 communication method. It accurately converts messages between CAN and RS-232 networks. This module let you to communicate with CAN devices easily from any PC or devices with RS-232 interface.

Moreover, we expand the functionalities of I-7530/I-7530T/I-7530FT for some special application. In pair connection mode, I-7530/I-7530T/I-7530FT can be used to connect PC with other RS-232 devices at the same time. The application architecture may be as follows.

3000V isolation on CAN side (for I-7530/I-7530T) 
The CAN port of I-7530/I-7530T is an isolated with 3000V isolation. This isolation can protect the local RS-232 devices from the damage signal coming from CAN network.

Watchdog inside
The watchdog is a hardware reset circuit to monitor the operation status. When working in harsh or noisy environment, the I-7530/I-7530T/I-7530FT may shut down by the external signal. The circuit may let the I-7530/I-7530T/I-7530FT to work continuously and never halt.

Power and Error indicator display
There are two indicators on the I-7530/I-7530T/I-7530FT.The power indicator can help user to check whether the I-7530/I-7530T/I-7530FT is standby or transmitting/receiving messages. The Error indicator will be turned on when some errors occur on the I-7530/I-7530T/I-7530FT.

  • Control System
  • Building Automation
  • Factory Automation
  • Distributed data acquisition
  • CAN bus Baud rate configuration
  • CAN acceptance filter configuration
  • CAN 2.0A or 2.0B specific selection
  • RS-232 Baud rate and data bit setting
  • RS-232 responded selection
  • Easy test to transmit/receive can messages
  • Setting for I-7530/I-7530T/I-7530FT communication mode (normal mode or pair connection mode)
  • It has a CAN message field which can display the receiving CAN messages in Decimal or HEX mode
  • Can display the timestamp of each received CAN message
  • Users can change the display mode, up-down, down-up or stop
  • It can count the number of received CAN messages
  • Data Log : It can save the CAN message as “ txt ” file
  • Has CAN ID filter function
  • Can send CAN message to CAN BUS according the defined interval time

Item Description

CAN bus Power Meter
This is the software solution for the CAN bus power meter(PM-213x-CAN). It is convenient to collect the distributed power information via CAN bus. [more…]

CAN OPC Server
This is the OPC server for all the SCADA like LabVIEW, iFix, DASYLab and etc. By using the OPC server, the users be able to control any CAN devices via the famous SCADA. [more…]

VxCAN Driver
The VxCAN driver is the virtual CAN driver for all CAN converters and CAN master products. Even using different products, the users could use the same APIs to develop any CAN applications. [more…]

VxCAN Utility
The VxCAN Utility, a diagnostic and test software tool, is designed to unleash the power of all CAN products of ICP DAS. It is based on the Virtual CAN technique which creates the virtual CAN ports to match the physical CAN interfaces of the installed products. [more…]

InduSoft Driver
The IndoSoft is one of the famous and high performance SCADA. Nowaday, it supports the CAN, CANopen and DeviceNet driver for all the coresponding converter or master series products. [more…]

CANcheck
This is the software for diagnosing and testing the user’s CAN devices. The graphical interface is ready-made and easy to operate. [more…]

CAN Test Tool
The CAN test tool can help users to test the CAN communication of CAN series of ICP DAS by the simple steps. This tool is based on VxCAN driver and supports most of all CAN products of ICP DAS
The test is the performance which transfer 8 bytes data frame from CAN to RS232. (for I-7530/I-7530T)
CAN setting
Transfer frames
Transfer time(ms)
RS-232 setting
Receive frames
Receive time (ms)
The max frames/sec
Data<8 byes/frme
RS232 command length
2.0A 1Mbps
1,000
200
115200,n,8,1
1,000
2954
338
>=338
22 B
2.0A 1Mbps
1,000
200
115200,n,7,1
1,000
2775
360
>=360
22 B
2.0B 1Mbps
1,000
200
115200,n,8,1
1,000
3580
279
>=279
27 B
2.0B 1Mbps
1,000
200
115200,n,7,1
1,000
3337
299
>=299
27 B

 

The test is the performance which transfer 8 bytes data frame from RS232 to CAN. (for I-7530/I-7530T)
CAN setting
Transfer frames
Transfer time (ms)
RS-232 setting
Receive frames
Receive time (ms)
The max frames/sec
Data<8 byes/frame
RS232 command length
2.0A 1Mbps
1,000,000
2,612,243
115200,n,8,1
1,000,000
2,612,243
382
>=382
22 B
2.0A 1Mbps
1,000,000
2,441,130
115200,n,7,1
1,000,000
2,441,130
409
>=409
22 B
2.0B 1Mbps
1,000,000
3,142,043
115200,n,8,1
1,000,000
3,142,043
318
>=318
27 B
2.0B 1Mbps
1,000,000
3,142,043
115200,n,7,1
1,000,000
2,966,646
337
>=337
27 B
Item
I-7530
I-7530T
I-7530-FT
Hardware
EEPROM
2 KB (for system information), 100,000 erase/write cycles
CAN Interface
Transceiver
NXP 82C250
NXP TJA1042
AMIS 41682
Channel number
1
Connector
9-pin male D-Sub (CAN_L, CAN_H, N/A for others)
Baud Rate (bps)
10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, 1 Mbps
(allow user-defined CAN baud rate)
10 k, 20 k, 50 k, 125 k (allow user-defined CAN baud rate)
Isolation
3000 VDC for DC-to-DC,
2500 Vrms for photo-couple
NONE
Terminal Resistor
Selectable 120Ω terminal resistor by jumper
1 kΩ for CAN_H and CAN_L
Specification
ISO-11898-2, CAN 2.0A and CAN 2.0B
ISO-11898-3 (low speed fault tolerance), CAN 2.0A and CAN 2.0B
Receive Buffer
1000 data frames
RS-232 Interface
Connector
9-pin female D-Sub (TxD, RxD, GND, N/A for others )
Baud Rate (bps)
110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps
Data bit
5, 6, 7, 8
Stop bit
1, 2
Parity bit
None, Even, Odd
Receive Buffer
900 data frames
LED
Round LED
ON LED: Power and Data Flow; ERR LED: Error Status
Power
Protection
Power reverse polarity protection, Over-voltage brown-out protection
Power Consumption
1 W
Mechanism
Installation
DIN-Rail
Dimensions
72mm x 118mm x 33mm (W x L x H)
Environment
Operating Temp.
-25 ~ 75 ℃
Storage Temp.
-30 ~ 80 ℃
Humidity
10 ~ 90% RH, non-condensing
I-7530T-G     CR Intelligent RS-232 to CAN converter with TJA1042 Transceiver(RoHS)
CNT-CAN CAN bus Connector
CA-0910-C 9-pin Female D-sub & 3-wire CAN bus cable (1M)
SG-770 7/14 channel Surge Protector
4PCD-002 EMI Ferrite Split/Snap-On Core
M12A-5P-IP68 Field-Installation A-coded 5-pin Female