Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » RS-485 I/O Modules » I-7000 » Module RS-485 DCON 5 kênh đầu ra DC SSR + 4 kênh đầu vào số (DI) ICP DAS I-7065B CR

Module RS-485 DCON 5 kênh đầu ra DC SSR + 4 kênh đầu vào số (DI) ICP DAS I-7065B CR

4-ch Isolated DI (Wet, 4~30 VDC) and 5-ch DC-SSR Output Module

Chia sẻ:
Model: I-7065B CR
Views: 338

Module RS-485 DCON 5 kênh đầu ra DC SSR + 4 kênh đầu vào số (DI) ICP DAS I-7065B CR

The I-7063B module provides 8 digital input channels and 3 DC SSR output channels, and the I-7065B provides 4 digital input channels and 5 DC SSR output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. In comparison to electromechanical relays, SSR technology provides a faster response time and greater electrical endurance. The integration of DC SSR technology also eliminates potential for arcing, bounce, and switching noise. The I-7063BD provides 11 LED indicators and the I-7065BD/M-7065BD provides 9 LED indicators that can be used to monitor the status of the digital input and SSR output. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments. The M-7065B supports both the Modbus RTU and DCON protocols, which can be configured via software.

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
Models I-7063B/I-7063BD I-7065B/I-7065BD M-7065B/M-7065BD
DC Solid State Relay Output
Channels 3 5
Relay Type DC-SSR (Form A)
Form A
DC-SSR
Operating Voltage Range 3 ~ 30 VDC
Max. Load Current 1 A
Leakage Current 0.1 mA
Min. Operate Time 1 ms
Min. Release Time 1 ms
Dielectric Strength 3500 VDC
Electrical Endurance Long Life, No Arcing, No Bounce, No Switching Noise
Power-on Value Yes
Safe Value Yes
Digital Output
Channels 8 4
Type Dry Contact
Wet Contact Sink/Source
Wet Contact On Voltage Level +1 VDC Max.
Off Voltage Level +4 ~ 30 VDC
Dry Contact On Voltage Level
Off Voltage Level
Effective Distance
for Dry Contact
Counters Max. Count 65535 (16-bit)
Max. Input Frequency 100 Hz
Min. Pulse Widt 5 ms
Input Impedance 3 kΩ
Channel-to-Channel Isolation
Overvoltage Protection ±35 VDC
Models I-7063B I-7063BD I-7065B I-7065BD M-7065B M-7065BD
Communication
Interface RS-485
Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate 1200 ~ 115200 bps
Protocol DCON Modbus RTU, DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator Yes, 1 LED as Power/Communication Indicator
I/O LED Indicators Yes, 11 LEDs as
Digital Input/
Relay Output
Indicators
Yes, 9 LEDs as
Digital Input/
Relay Output
Indicators
Yes, 9 LEDs as
Digital Input/Relay
Output Indicators
7-Segment LED Display
Isolation
Intra-Module Isolation, Field-to-Logic 3750 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±2 kV for Power Line
Surge (IEC 61000-4-5)
Power
Reverse Polarity Protection Yes
Input Range 10 ~ 30 VDC
Consumption 0.5 W 1.0 W 0.6 W 1.0 W 0.6 W 1.0 W
Mechanical
Dimensions (W x L x H) 72 mm x 123 mm x 35 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +85°C
Humidity 10 ~ 95% RH, Non-condensing
I-7065B     CR 4-ch Isolated DI (Wet, 4~30 VDC) and 5-ch DC-SSR Output Module using DCON Protocol (Blue Cover) (RoHS)
tM-7520U CR RS-232 to RS-485 converter (RoHS)
tM-7561 CR USB to RS-485 converter (RoHS)
I-7514U CR 4-channel RS-485 Hub (RoHS)
SG-3000 series Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Inputs