4-ch Isolated DI (Wet, 4~30 VDC) and 5-ch AC-SSR Output Module

Chia sẻ:
Model: I-7065A CR
Views: 310

Module RS-485 DCON 5 kênh đầu ra AC SSR + 4 kênh đầu vào số (DI) ICP DAS I-7065A CR

The I-7063A module provides 8 digital input channels and 3 AC SSR(Solid State Relay) output channels, and the I-7065A provides 4 digital input channels and 5 AC SSR output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. In comparison to electromechanical relays, SSR technology provides a faster response time and greater electrical endurance. The integration of AC SSR technology also eliminates potential for arcing, bounce, and switching noise. The I-7063AD provides 11 LED indicators and the I-7065AD provides 9 LED indicators that can be used to monitor the status of the digital input and SSR output. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments.

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
Models I-7063A I-7063AD I-7065A I-7065AD
AC Solid State Relay Output
Channels 3 5
Relay Type AC-SSR (Form A)
Form A
AC-SSR
Operating Voltage Range 24 ~ 265 VAC
Max. Load Current 1 A
Leakage Current 1.5 mA
Min. Operate Time 1/2 cycle + 1 ms
Leakage Current 1/2 cycle + 1 ms
Dielectric Strength 2500 VDC
Electrical Endurance Long Life, No Arcing, No Bounce, No Switching Noise
Power-on Value Yes
Safe Value Yes
Digital Input/Counter
Channels 8 4
Type Dry Contact
Wet Contact Sink/Source
Wet Contact On Voltage Level +1 VDC Max.
Off Voltage Level +4 ~ 30 VDC
Dry Contact On Voltage Level
Off Voltage Level
Effective Distance
for Dry Contact
Counters Max. Count 65535 (16-bit)
Max. Input Frequency 100 Hz
Min. Pulse Widt 5 ms
Input Impedance 3 kΩ
Channel-to-Channel Isolation
Overvoltage Protection ±35 VDC
Models I-7063A I-7063AD I-7065A I-7065AD
Communication
Interface RS-485
Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate 1200 ~ 115200 bps
Protocol DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator Yes, 1 LED as Power/Communication Indicator
I/O LED Indicators Yes, 11 LEDs as Digital Input/Relay Output Indicators Yes, 9 LEDs as Digital Input/Relay Output Indicators
7-Segment LED Display
Isolation
Intra-Module Isolation, Field-to-Logic 3750 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±2 kV for Power Line
Surge (IEC 61000-4-5)
Power
Reverse Polarity Protection Yes
Input Range 10 ~ 30 VDC
Consumption 0.5 W 1.0 W 0.6 W 1.0 W
Mechanical
Dimensions (W x L x H) 72 mm x 123 mm x 35 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +85°C
Humidity 10 ~ 95% RH, Non-condensing