Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » RS-485 I/O Modules » I-7000 » Module RS-485 DCON 8 kênh đầu vào số cách ly ICP DAS I-7052D-G CR

Module RS-485 DCON 8 kênh đầu vào số cách ly ICP DAS I-7052D-G CR

8-ch Isolated DI (Wet) Module with LED Display

Chia sẻ:
Model: I-7052D-G CR
Views: 446

Module RS-485 DCON 8 kênh đầu vào số cách ly ICP DAS I-7052D-G CR

The I-7052 offers 6 fully independent channels and 2 common ground channels for digital input. The diffential inputs feature channel-to-isolation. In addition, you can choose either sink- or source-type input via wire connections. All channels are able to be used as 16-bit has 8 LED indicators for DI channel status monitoring. 4 kV ESD protection and 5000 Vrms intra-module isolation are standard. The M-7052 has the same hardware specifications as the I-7052, but provides additional support for the Modbus RTU protocol as well as the DCON protocol. The I-7053_FG features a long effective distance measurement for dry contact digital input of up to 500 meters. The I-7053_FG supports source-type input. All 16 channels are also able to be used as 16-bit counters, each of which are non-isolated. The I-7053D_FG has 16 LED indicators for channel status monitoring. The M-7053 has the same hardware specifications as the I-7053_FG, but provides additional support for the Modbus RTU protocol as well as the DCON protocol.

• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Display
Type I/O LED Indicator
Isolation
Intra-module Isolation 5000 Vrms
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Point
LED Indicators
Status 1 x Power and Communication
8 x Digital Input
Digital Input/Counter
Channels 8
Type Wet Contact
Sink/Source (NPN/PNP) Sink/Source
Wet Contact, ON Voltage Level +4 ~ 30 VDC
Wet Contact, OFF Voltage Level +1 VDC Max.
Max. Counts 65535 (16-bit)
Frequency 100 Hz
Min. Pulse Width 5 ms
Input Impedance 3 KΩ
Overvoltage Protection ±35 VDC
Channel-to-Channel Isolation Yes, ±2 kV for differential only
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 0.6 W
Mechanical
Dimensions (mm) 123 x 72 x 35 (W x L x H)
Installation DIN-Rail
Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
I-7052D-G     CR 8-ch Isolated DI (Wet) Module with LED Display using DCON Protocol (Gray Cover) (RoHS)
TOP HOME