Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » RS-485 I/O Modules » I-7000 » Module RS-485 DCON 2 kênh đầu vào 4-Wire Full-Bridge Strain Gauge+4 DO+1 DO ICP DAS I-7016D CR

Module RS-485 DCON 2 kênh đầu vào 4-Wire Full-Bridge Strain Gauge+4 DO+1 DO ICP DAS I-7016D CR

2-ch 4-wire Strain Gauge Input Module with LED Display

Chia sẻ:
Model: I-7016D CR
Views: 943

Module RS-485 DCON 2 kênh đầu vào 4-Wire Full-Bridge Strain Gauge+4 DO+1 DO ICP DAS I-7016D CR

In the industrial environment, there are numerous examples where force needs to be converted into a measurable electrical output. In most cases, a strain gauge or a load cell can be used. But the question is, how do we then deal with these electrical output measurements? In this situation, the I-7016 is definitely the No. 1 choice. Not only can the module process data from a load cell or a strain gauge, it also features linear mapping that can be used to directly convert the resulting data into weight via a user-defined correspondent table. The I-7016 supports full-bridge strain gauges and provides 2 Analog Input channels, 1 excitation voltage output channel, 1 Digital Input channels and 4 Digital Output channels. The module provides a programmable input range (±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, and ±2.5 V) and each Analog Input channel can be individually configured. Excitation voltage output can be in the range of 0 ~ +10 V, with a 40 mA driving efficiency. Digital Output channels can also be set as high or low alarm outputs. The M-7016 supports both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7016.
  • Tự động hóa tòa nhà
  • Tự động hóa nhà máy
  • Máy tự động
  • Bảo trì từ xa
  • Chẩn đoán từ xa
  • Kiểm tra trang thiết bị
CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Display
Type 5-Digit 7 Segment LED Display
Isolation
Intra-module Isolation 1500 VDC
LED Indicators
Status 1 x Power and Communication
Digital Input/Counter
Channels 1
Type Dry Contact
Sink/Source (NPN/PNP) Source
ON Voltage Level Close to GND
OFF Voltage Level Open
Max. Counts 16-bit
Frequency 50 Hz
Input Impedance 3 kΩ
Overvoltage Protection ±30 VDC
Digital Output
Channels 4
Type Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +3.5 ~ +50 VDC
Load Current 30 mA/Channel
Power on Value Yes
Safe Value Yes
Strain Gauge, Load Cell Input
Channels 2
Type Strain Gauge
Wiring Full-Bridge
Accuracy ±0.05% of FSR
Resolution 16-bit
Sampling Rate 10 Hz for 1-channel mode or 2 Hz (total) for 2-channel mode
Impedance 20 MΩ
Overvoltage Protection ±5 VDC
Excitation Voltage Output
Channels 1
Range 0 ~ +10 V
Resolution 16-bit
Accuracy ±0.05%
Max. Load Current 40 mA
Power on Value Yes
COM Ports
Ports 1 x RS-485
Baud Rate 1200 to 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 3.0 W
Mechanical
Dimensions (mm) 123 x 72 x 35 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
I-7016D     CR 2-ch 4-wire Strain Gauge Input Module with LED Display using DCON Protocol (Blue Cover) (RoHS)
TOP HOME