Trang chủ » Truyền thông công nghiệp » Bộ chuyển đổi CAN sang quang Multi-mode ST ICP DAS I-2533 CR

Bộ chuyển đổi CAN sang quang Multi-mode ST ICP DAS I-2533 CR

CAN to Multi-mode Fiber Bridge

Chia sẻ:
Model: I-2533 CR
Views: 855

Bộ chuyển đổi CAN sang quang Multi-mode ST ICP DAS I-2533 CR

The I-2533 is an intelligent CAN bridge that can be used to establish the connection between two CAN bus systems via fiber optic cable. Similar to the I-2532, the I-2533 can also apply in various CAN-based protocols to convert CAN bus signals to optical signals and reshape the CAN signals. The difference between the I-2532 and I-2533 is the CAN configuration functions and the distance limitation of CAN communication. The I-2533 offers the functions to configure the CAN baud rate and CAN message filters. These are useful when using the I-2533 to link two CAN networks which may have different baud rates. By using the I-2533, the transmission distance limitation of the CAN bus system will not be reduced because of the CAN baud rate, which means that the total network length can be extended. This feature means that users can develop the applications more powerful and flexible with the I-2533.

  • Control System
  • Building Automation
  • Factory Automation
  • Distributed data acquisition
LED Indicators
Status 1 x Power
3 x CAN status
1 x Fiber
COM Ports
Ports 1 x RS-232 (Utility Port)
Fiber
Ports Multi Mode; ST connector x 1
Fiber Cable 50/125, 62.5/125 or 100/140 μm (62.5/125μm is recommended)
Wavelength 850 nm
Propagation Delay 250 us
Distance Between Stations 2 km max (62.5 / 125 μm recommended)
CAN
Ports 1
Baud Rate 10 k ~ 1 M bps
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Terminal Resistor Switch for 120Ω terminal resistor
Specification ISO-11898-2, CAN 2.0A and CAN 2.0B
Filter Yes
Power
Input Range +10 VDC ~ +30 VDC
Consumption 3 W
Mechanical
Casing Plastic
Dimensions (mm) 32.3 x 77.5 x 99.0 (W x L x H)
Installation DIN-Rail
Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing

Specification Memo

Note1:
The propagation delay depends on the CAN Bus baud rate and the CAN message format. This value has been tested using a CAN baud rate of 1 Mbps, the CAN ID 0x12345678 and 8 bytes of data with a value of 0xFF.
I-2533     CR CAN to Multi-mode Fiber Bridge; 1 (2 km) multi-mode, ST connector (RoHS)
TOP HOME