Bộ chuyển đổi cổng Modbus TCP Server sang M-Bus Master ICP DAS GW-7838-M CR

Modbus TCP Server to M-Bus Master Gateway

Chia sẻ:
Model: GW-7838-M CR
Views: 401

Bộ chuyển đổi cổng Modbus TCP Server sang M-Bus Master ICP DAS GW-7838-M CR

M-Bus (Meter-Bus) is a communication interface widely used in various meters, such as electricity meters, water meters, heat meters, etc. Ease of installation (two-wire system includes power and communication function) and robustness are the most important features. M-Bus has its own physical layer and protocol. Therefore, it is usually switched to other systems, such as Modbus, to facilitate the overall application.
In the field of automation, Modbus TCP is one of the most common communication standards. ICP DAS developed the gateway GW-7838-M for Modbus TCP to M-Bus, allows the direct transmission of meter data to a control system using Modbus TCP. The GW-7838-M supports operating up to 100 devices on the M-Bus. After an initial configuration by M-Bus utility, GW-7838-M will read out the meters data autonomously. The PLC or PC as a Modbus TCP client can access meter data via a TCP connection easily.

The M-Bus (Meter‐Bus) is a bus optimized for the reading of measurement instruments like: energy counters, hot and cold water counters, gas, pressure, sensors and actuators, etc.….

COM Ports
Ports 1 x RS-232, Non-isolated
Baud Rate 300 ~ 115200 bps
Parity None, Even, Odd, Mark, Space
Data Bit 5, 6, 7, 8
Stop Bit 1, 2
Ethernet
Ports 1 x RJ-45, 10/100Base-T(X)
Protocol Modbus TCP
M-Bus
Ports 1
Baud Rate 300 ~ 2400 bps and user-defined baud rate
Data Bit 5, 6, 7, 8
Stop Bit 1, 2
Parity None, Even, Odd, Space, Mark
Isolation 3750 Vrms for photo-couple
Current Protection short-circuit protection
Power
Consumption 1.8 W @ 24 VDC (with 1 slave device), 11.8 W @ 24 VDC (with 100 slave devices)
Mechanical
Dimensions (mm) 102 x 123 x 40 (W x H x D)
Installation Wall mounting
Environmental
Operating Temperature -25 ~ +75 ℃
Storage Temperature -30 ~ +80 ℃
Humidity 10 ~ 90% RH, Non-condensing
  • Provide M-Bus and serial bus user-defined baud rate
  • Check firmware version
  • Configure meters list of M-Bus gateway
  • Test reading meters data
  • Update firmware
Baud Rate Selection by DIP Switch
DIP 3 ~ 6 0000 1000 0100 1100 0010 1010
Baud [bps] 300 600 1200 2400 4800 9600
DIP 3 ~ 6 0110 1110 0001 1001 Others
Baud [bps] 19200 38400 57600 115200 User-defined
The status of DIP bit 0 is OFF and 1 is ON.
The default data format of serial bus baud rate is 8, n, 1.
The default data format of M-Bus bus baud rate is 8, e, 1.
Execution Mode by DIP Switch
DIP 1 (Init) DIP 2 (Mode) Description
OFF OFF Run Firmware
OFF ON Configure
ON OFF Update Firmware
Support Meter
The following meters have been tested with the GW-7838-M communication:
Manufacture Picture Model Type Meter Type
Danfoss SONOMETER 500 Heat Meter
SENSUS 405S Water Meter
WESER PUL Heat Meter
DIEHL ALTAIR V4 Water Meter
Wason LXZD-Y3 Water Meter
GW-7838-M     CR Modbus TCP Server to M-Bus Master Gateway (Metal Case)(RoHS)

 