Bộ chuyển đổi Modbus TCP/RTU/ASCII Slave sang DeviceNet Master ICP DAS GW-7434D-G CR

Modbus TCP/RTU/ASCII Slave to DeviceNet Master Gateway

Chia sẻ:
Model: GW-7434D-G CR
Views: 574

Bộ chuyển đổi Modbus TCP/RTU/ASCII Slave sang DeviceNet Master ICP DAS GW-7434D-G CR

The GW-7434D is an economic solution that provides a communication protocol transformation between the DeviceNet protocol and the Modbus TCP protocol. This module solves the problem to connect an existing DeviceNet network to the Ethernet-based PLC, HMI or SCADA for setting up a control or monitoring system. Different to the GW-7243D, the GW-7434D offers the Predefined Master connection Set function and Group 2 only Server function as a DeviceNet master, and enables accessing the DeviceNet slaves automatically and cyclically. If the PLC, HMI or SCADA would like to access the DeviceNet slaves and simultaneously communicate with the Modbus slaves or COM-based devices connected with the RS-232 or RS-485 port of the GW-7434D, the GW-7434D can be the Modbus TCP server or VxComm server to exchange the data with those devices.

DeviceNet Gas Valve Station (EN)
Robotic Arm Control (TC)

Robotic Arm Control (EN)

Touched HMI Aplications (EN)

 


Typical Applications

Application 1: Modbus TCP/RTU slave to DeviceNet master gateway

The GW-7434D can act as a Modbus TCP/RTU slave to DeviceNet master gateway. Using the module, users don’t need to take care of the detail of the DeviceNet protocol. The module will implement the DeviceNet protocol automatically. It mainly supports the Predefined Master/Slave Connection Set functions to allow users to merge I/O data into DeviceNet network by using Modbus TCP/RTU commands.

Application 2: a single Modbus/TCP to multi-Mosbus/RTU converter

GW-7434D can be a single Modbus/TCP to multi-Modbus/RTU converter. You can simple use the Utility software to configure the device and then set connection between SCADA, HMI software and the GW-7434D.

Application 3: protocol converter with VxComm technique

GW-7434D can also be able to link to serial devices that don’t support Modbus/RTU. To use this function, you will need to install VxComm driver on host PCs. After installation, you will be able to access the remote COM ports via the standard serial driver.

The GW-7434D provides centralized data storage, “Internal Memory”, for data that is shared between the DeviceNet and Modbus/TCP network. Data is placed into the “Internal Memory” by one network interface, allowing the data to be read/wrote through the other network interface.

We provide GW-7434D Utility tools for Windows 98/SE/2K/XP, it includes:

  • Online add/remove DeviceNet devices via Ethernet
  • Online monitor and configure devices status via Ethernet
  • Get/Set Modbus/TCP input/output memory address
  • Support DeviceNet I/O mapping table
  • Show DeviceNet devices connection status
  • Support communication mode setting

Application 1: Modbus TCP/RTU slave to DeviceNet master gateway
The GW-7434D can act as a Modbus TCP/RTU slave to DeviceNet master gateway. Using the module, users don’t need to take care of the detail of the DeviceNet protocol. The module will implement the DeviceNet protocol automatically. It mainly supports the Predefined Master/Slave Connection Set functions to allow users to merge I/O data into DeviceNet network by using Modbus TCP/RTU commands.

Application 2: a single Modbus/TCP to multi-Mosbus/RTU converter
GW-7434D can be a single Modbus/TCP to multi-Modbus/RTU converter. You can simple use the Utility software to configure the device and then set connection between SCADA, HMI software and the GW-7434D.

Application 3: protocol converter with VxComm technique
GW-7434D can also be able to link to serial devices that don’t support Modbus/RTU. To use this function, you will need to install VxComm driver on host PCs. After installation, you will be able to access the remote COM ports via the standard serial driver.

Hardware
EEPROM
16 KB; Data retention: 40 years; 1,000,000 erase/write cycles
Watchdog
Watchdog IC
CAN Interface
Controller
NXP SJA1000T with 16 MHz clock
Transceiver
NXP 82C250
Connector
5-pin screwed terminal block (CAN_L, CAN_H, N/A for others)
Isolation
1000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Protocol
DeviceNet Volume I ver2.0, Volume II ver2.0
UART Interface
COM 1
RS-232
COM 1 Connector
5-pin screwed terminal block (TxD, RxD, RTS, CTS, GND )
COM 2
RS-485 (Self-turner inside)
COM 2 Connector
2-pin screwed terminal block (DATA+, DATA-)
Ethernet Interface
Controller
10/100Base-TX Ethernet Controller (Auto-negotiating, Auto_MDIX)
Connector
RJ-45 with LED indicator
Protocol
Modbus TCP
Power
Power supply
Unregulated +10 ~ +30 VDC
Protection
Power reverse polarity protection, Over-voltage brown-out protection
Power Consumption
2.5 W
Mechanism
Dimensions
72mm x 122mm x 33mm (W x L x H)
Environment
Operating Temp.
-25 ~ 75 ℃
Storage Temp.
-30 ~ 80 ℃
Humidity
10 ~ 90% RH, non-condensing
GW-7434D-G     CR Modbus/TCP server to DeviceNet master Gateway (RoHS)