Model: GW-5492
Views: 1340

Bộ chuyển đổi BACnet/IP sang Modbus RTU kết nối RS-232/RS-485 ICP DAS GW-5492

GW-5492 is a fully configurable universal Modbus RTU to BACnet/IP gateway. The GW-5492 includes BACnet/IP Server and Modbus RTU Master which is used to make Modbus RTU devices accessible on a BACnet network. BACnet (Building Automation and Control Networking) protocol has been designed specifically to meet the communication needs of building automation and control systems for applications such as heating, ventilating, air-conditioning control…etc. The GW-5492 contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV) gives you flexibility in mapping Modbus RTU registers to any combination of BACnet objects. Multiple BIBBs (DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM, DS-COV-B…etc.) are supported. All the data transfer is configurable using a standard Web browser.

  • Building Automation
  • Heating, Ventilating, and Air-conditioning Control
  • Lighting Control
  • Access Control
  • Fire Detection Systems

CPU Module
CPU 32-bit
EEPROM 16 KB
Flash 64 MB
SRAM 64 MB
COM Ports
Ports COM1: RS-232 (RxD, TxD, and GND); Non-isolation
COM2: RS-485 (D2+, D2-); 2500 VDC; isolated
Ethernet
Ports 1 x RJ-45, 10/100/1000Base-TX
BACnet/IP
Modbus Modbus RTU Master
Objects AI, AO, AV, BI, BO, BV, MSI, MSO, MSV (Maximum: 200 each)
BIBBs DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DS-COV-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B, DM-UTC-B, DM-RD-B
Power
Input Range +10 ~ +30 VDC
Consumption 4.8 W (0.2 A @ 24 VDC)
Mechanical
Casing Plastic
Dimensions (mm) 91 x 132 x 52
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +85 °C
Humidity 5 ~ 90% RH, Non-condensing
GW-5492
BACnet/IP to Modbus RTU Gateway