Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Bộ điều khiển lập trình nhúng mở rộng 4 cổng I/O 2 cổng Ethernet Modbus TCP ICP DAS ET-8KP4-MTCP CR

Bộ điều khiển lập trình nhúng mở rộng 4 cổng I/O 2 cổng Ethernet Modbus TCP ICP DAS ET-8KP4-MTCP CR

4-slot Intelligent Ethernet I/O Expansion Unit (Modbus TCP Protocol)

Chia sẻ:
Model: ET-8KP4-MTCP CR
Views: 616

Bộ điều khiển lập trình nhúng mở rộng 4 cổng I/O 2 cổng Ethernet Modbus TCP ICP DAS ET-8KP4-MTCP CR

ET-8KP8-MTCP series is a Modbus TCP I/O expansion unit to expand I-8K and I-87K series I/O modules over the Ethernet for industrial monitoring and controlling applications. It offers two Ethernet switch ports for daisy-chain topology. The daisy-chain feature allows ET-8KP8 to connect in series to each other or other Ethernet devices. Users can easily simplify the cabling and save installation space with the feature. It is designed to be used in harsh and noisy environment, so the hardware is manufactured with wide power input range (10 ~ 30 VDC), isolated power input and can operate under wide temperature (-25 ~ +75 °C).

There are more than 90 I/O modules supported with the unit, including analog input/output, digital input/output, DI counter modules. To simplify installation and maintenance of I/O modules, it provides many useful features, such as: auto configuration, LED indicators for fault detection, dual watchdog to keep alive, programmable power on and safe values for safety. Modbus is a very wide known protocol in the industrial manufacturing and environment monitoring fields. Many SCADA software, HMI and PLC has builtin driver to support Modbus devices. Besides, we also provide SDK on different platforms, such as Windows XP, Window CE 5.0/6.0, Linux, MiniOS7. Therefore, it is very easy to integrate remote I/O to customer’s applications.

Display
Type 5 x Digit 7 Segment LED Display
LED Indicators
Status 1 x Run, 1x Module offline, 1 x WDT, 1 x Power
I/O Expansion
I/O Type I-87K, I-8K Series
Slots 4
COM Ports
Ports 1 x RS-232 (Console)
Protocol Modbus RTU/ASCII Slave
HMI
Push Button 4
Ethernet
Ports 2 x RJ-45, 10/100 Base-TX
Protocol Modbus TCP Slave, Modbus TCP to RTU Gateway
Power
Input Range +10 ~ 30 VDC (1 kV Isolated )
Redundant Power Inputs Yes
Consumption 2.0 W
Mechanical
Dimensions (mm) 188 x 132 x 111 (W x L x H)
Installation DIN-Rail, Wall mounting
Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +75 °C
Humidity 10 ~ 90 % RH, Non-condensing
ET-8KP4-MTCP     CR 4-slot Intelligent Ethernet I/O Expansion Unit (Modbus TCP Protocol) (RoHS)