Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module 2 cổng Ethernet Modbus TCP 4 kênh đầu ra relay ICP DAS ET-2268

Module 2 cổng Ethernet Modbus TCP 4 kênh đầu ra relay ICP DAS ET-2268

Ethernet I/O Module with 2-port Ethernet Switch, 4-ch Form A Relay Output and 4-ch Form C Relay Output (RoHS)

Chia sẻ:
Model: ET-2268
Views: 620

Module 2 cổng Ethernet Modbus TCP 4 kênh đầu ra relay ICP DAS ET-2268

Providing a variety of digital I/O functions, the ET-2268 module is an Ethernet I/O monitoring and control module. The module can be remotely controlled through a 10/100 M Ethernet network by using Modbus TCP/UDP protocol. Modbus has become a de facto standard communications protocol industrial application, and is now the most commonly available means of connecting industrial electronic devices. This makes the ET-2268 module being perfectly integrated with the HMI, SCADA, PLC or other software systems.

The ET-2268 provides 4 Form A signal Relay output and 4 Form C signal Relay Output channels. With 2 Ethernet ports, the ET-2268 allows daisy chain connection which enables flexibility in locating devices; easy installation and lower infrastructure costs. This module includes 8 LED indicators that can be used to monitor the Relay Output status, and options are provided that allow power-on and safe Digital Output values to be configured. It features 8 kV ESD, 4 kV EFT and 3 kV surge protection to enhance noise protection capabilities in industrial environments. The ET-2268 is the ideal solution for small signal switching.

The module can be used to create DI to DO pair-connect through the Ethernet. After configuration, the ET-2268 module can poll the status of remote DI channels via the Modbus TCP protocol and write data to local DO channels.

It is equipped with removable terminal block connector for easy and robust wiring in industrial applications, and features a powerful 32-bit ARM MCU to handle efficient network trafficking.

Factory, Building and Home Automation Remote Maintenance

Software
Built-in Web Server Yes
CPU Module
CPU 32-bit ARM
Watchdog Timer Module, Communication (Programmable)
Isolation
2-way Isolation Ethernet: 1500 VDC
I/O: 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±8 kV Contact for Each Terminal
±16 kV Air for Random Point
Surge (IEC 61000-4-5) ±3 kV for Power Line
LED Indicators
Status Run, Ethernet, I/O
Relay Output
Channels 8 (Form A x 4, Form C x 4)
Type Signal Relay
Contact Material Siler Nickel, Gold-covered
Contact Rating 2 A @ 30 VDC
0.24 A @ 220 VDC
0.25 A @ 250 VDC
Operate Time 3 ms (typical)
Release Time 4 ms (typical)
Electrical Endurance 2 x 10^5 ops
Mechanical Endurance 10^8 ops
Surge Strength 2000 VDC
Power on Value Programmable
Safe Value Programmable
Ethernet
Ports 2 x RJ-45, 10/100 Base-TX, Switch Ports
LAN bypass Yes
Security Password and IP Filter
Protocol Modbus TCP, Modbus UDP, and MQTT
Power
Reverse Polarity Protection Yes
Consumption 3.3 W (max.)
Powered from Terminal Block +10 to +30 VDC
Mechanical
Casing Plastic
Dimensions (mm) 33 x 126 x 108 (W x L x H)
Installation DIN-Rail mounting
Environment
Operating Temperature -25 to +75 °C
Storage Temperature -40 to +80 °C
Humidity 10 to 90% RH, Non-condensing
ET-2268     CR  Ethernet I/O Module with 2-port Ethernet Switch, 4-ch Form A and 4-ch Form C Signal Relay (RoHS)
TOP HOME