Trang chủ » Module vào/ra tương tự/số kết nối RS-485/Ethernet » Module 2 cổng Ethernet Modbus TCP 6 kênh đầu ra relay ICP DAS ET-2260

Module 2 cổng Ethernet Modbus TCP 6 kênh đầu ra relay ICP DAS ET-2260

Ethernet I/O Module with 6-ch DI and 6-ch Power Relay

Chia sẻ:
Model: ET-2260
Views: 499

Module 2 cổng Ethernet Modbus TCP 6 kênh đầu ra relay ICP DAS ET-2260

Providing various digital I/O functions, the ET-2260 module is an IP-based Ethernet I/O monitoring and control module. The module can be remotely controlled through a 10/100 M Ethernet network by using Modbus TCP/UDP protocol. Modbus has become a de facto standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices. This makes the ET-2260 module perfect integration with the HMI, SCADA, PLC and other software systems.

The ET-2260 provides 6 wet contact Digital Input channels and 6 Form A electromechanical Relays. With 2 Ethernet ports, the ET-2260 allows daisy chain connection which permits the flexibility in locating devices, eases installation and lowers infrastructure costs. It features 8 kV ESD protection, 4 kV EFT protection, 3 kV surge and 3750 VDC I/O isolation are also provided to enhance noise protection capabilities in industrial environments. Each input channel can be used as a 32-bit counter. The power-on value and safe value of relay are configurable.

The module can be used to create DI to DO pair-connect through the Ethernet. After configuration, the ET-2260 module can poll the status of the local DI channels and then use the Modbus/TCP protocol to continuously write to the remote DO devices.

It is equipped with removable terminal block connector for easy and robust wiring in industrial situations, and features a powerful 32-bit ARM MCU to handle efficient network trafficking.

  • Factory, Building and Home Automation
  • Remote Maintenance
Software
Built-in Web Server Yes
CPU Module
CPU 32-bit ARM
Watchdog Timer Module, Communication (Programmable)
Isolation
2-way Isolation Ethernet: 1500 VDC
I/O: 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±8 kV Contact for Each Terminal
±16 kV Air for Random Point
Surge (IEC 61000-4-5) ±3 kV for Power Line
LED Indicators
Status Run, Ethernet, I/O
Digital Input/Counter
Channels 6
Type Dry Contact
Wet Contact
Sink/Source (NPN/PNP) Dry: Source
Wet: Sink/Source
ON Voltage Level Dry: Close to GND
Wet: +10 to +50 VDC
OFF Voltage Level Dry: Open
Wet: +4 VDC (max.)
Max. Counts 4,294,967,295 (32-bit)
Frequency 3 kHz
Input Impedance 7.5 kΩ
Overvoltage Protection +70 VDC
Low Pass Filter 1 to 6500 ms (0.08 Hz to 500 Hz)
Relay Output
Channels 6
Type Power Relay, Form A (SPST N.O.)
Contact Rating 5 A @ 250 VAC/24 VDC (Resistive Load)
Operate Time 10 ms (max.)
Release Time 5 ms (max.)
Electrical Endurance 10^5 ops.
Mechanical Endurance 2 x 10^7 ops.
Power on Value Programmable
Safe Value Programmable
Ethernet
Ports 2 x RJ-45, 10/100 Base-TX, Switch Ports
LAN bypass Yes
Security Password and IP Filter
Protocol Modbus TCP, Modbus UDP, and MQTT
Power
Reverse Polarity Protection Yes
Consumption 3.3 W (max.)
Powered from Terminal Block +10 to +30 VDC
Mechanical
Casing Plastic
Dimensions (mm) 33 x 126 x 108 (W x L x H)
Installation DIN-Rail mounting
Environment
Operating Temperature -25 to +75 °C
Storage Temperature -40 to +80 °C
Humidity 10 to 90% RH, Non-condensing
ET-2260     CR  Ethernet I/O Module with 2-port Ethernet Switch, 6-ch Power Relay and 6-ch DI (RoHS)