Model | DR-120-24 | DR-120-48 |
Input | ||
Voltage range | 88 ~ 132 VAC/176 ~ 264 VAC by switch 248 ~ 370 VDC |
|
Frequency range | 47 ~ 63Hz | |
Efficiency (Typ.) | 85 % | 84 % |
AC Current (Typ.) | 2.6 A/115 VAC 1.6 A/230 VAC |
|
Inrush Current (Typ.) | Cold Start 20 A/115 VAC 40 A/230 VAC |
|
Leakage current | <3.5 mA / 240 VAC | |
Output | ||
DC Voltage | 24 V | 48 V |
Rated Current | 5 A | 2.5 A |
Current Range | 0 ~ 5 A | 0 ~ 2.5 A |
Rated power | 120 W | |
Ripple & noise (max.) Note.2 | 100mVp-p | |
Voltage ADJ. range | 24 ~ 28 V | 48 ~ 53 V |
Voltage Tolerance Note.3 | ±1.0% | |
Line Regulation | ±0.5% | |
Load regulation | ±1.0% | |
Setup, rise Time Note.5 | 500 ms, 70 ms/230 VAC 500 ms, 70 ms/115 VAC at full load |
|
Hold up time (Typ.) | 36 ms/230 VAC 32 ms/115 VAC at full load |
|
Protection | ||
Overload | 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed |
|
Over voltage | 29 ~ 33 V | 58 ~ 65 V |
Protection type : Shut down o/p voltage, re-power on to recover | ||
Environmental | ||
Working temp. | -10 ~ +60 °C (Refer to output load derating curve) | |
Working humidity | 20 ~ 90% RH non-condensing | |
Storage TEMP., humidity | -20 ~ +85 °C , 10 ~ 95% RH | |
TEMP. Coefficient | ±0.03%/°C (0 ~ 50°C) | |
Vibration | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | |
Safety & EMC (Note 4) | ||
Safety standards | UL508, UL60950-1, TUV EN60950-1 Approved | |
Withstand voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |
Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500 VDC | |
EMI Conduction & Radiation | Compliance to EN55011,EN55022 (CISPR22) Class B | |
Hsrmonic current | Compliance to EN61000-3-2,-3 | |
EMS immunity | Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A | |
DC OK Relay Contact | ||
Contact Close | When the output voltage reaches the adjusted output voltage. | |
Contact Open | When the output voltage drop below 90% output voltage. | |
Contact Ratings (max.) | 30V/1A resistive load | |
Others | ||
MTBF | 136.8Khrs min. MIL-HDBK-217F (25°C) |
|
Dimensions (W x H x D) | 65.5 x 125.2 x 100 mm | |
Packing | 0.79 Kg; 20 pcs/16.5 Kg/1.1 CUFT | |
NOTE | ||
|