Bộ đo 3 kênh điện áp 600VAC/VDC sang tín hiệu tương tự ICP DAS DN-843VI-600V CR

3-channel 600 VDC Voltage Attenuator with channel to channel isolation

Chia sẻ:
Model: DN-843VI-600V CR
Views: 907

The DN-843V/DN-843VI series and DN-848VI series are voltage input attenuator. The maximum input range is from ±10 Vpp to ±800 Vpp and can be attenuated to ±10 Vpp. The “I” version provide 3000 VDC intra-modules isolation and 3000 VDC channel to channel isolation to avoid the noise interference from inputs to outputs or channel to channel. It can be used with the analog input modules such as I-7017 and I-87017 etc. to measure the high voltage.

EMS Protection
ESD (IEC 61000-4-2) ±4 kV contact for power line, input and output channels,
±8 kV air for random point
Surge (IEC 61000-4-5) ±3 kV for power liner
Analog Input
Channels 3 : DN-843V-600V, DN-843VI-600V
8 : DN-848VI-10V, DN-848VI-80V, DN-848VI-150V
Type AC/DC Voltage
Range ±10 ~ ±800 Vpp
Accuracy 1% of FSR
Bandwidth 30 KHz : DN-848VI-10V, DN-848VI-80V, DN-848VI-150V
100 KHz : DN-843V-600V, DN-843VI-600V
Input Impedance >1 MΩ
Channel-to-Channel Isolation 3000 VDC (except DN-843V-600V)
Intra-module Isolation 3000 VDC (except DN-843V-600V)
Analog Output
Channels 3 : DN-843V-600V, DN-843VI-600V
8 : DN-848VI-10V, DN-848VI-80V, DN-848VI-150V
Type AC/DC Voltage
Range ±10 Vpp
Power
Input Range +10 ~ +30 VDC
Consumption 0.56 W : DN-843V-600V
3.84 W : DN-843VI-600V
9.2 W : DN-848VI-10V, DN-848VI-80V, DN-848VI-150V
Mechanical
Casing Plastic
Dimensions (mm) 174 x 122 x 25 (W x L x D) : DN-843V-600V, DN-843VI-600V
174 x 122 x 33 (W x L x D) : DN-848VI-10V, DN-848VI-80V, DN-848VI-150V
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +75 °C
Humidity 10 ~ 90% RH, Non-condensing
DN-843VI-600V     CR  3-channel ±600 Vpp Voltage Attenuator with channel to channel isolation (RoHS)