Trang chủ » Truyền thông công nghiệp » Module CANopen Slave 16 kênh đầu vào tương tự AI ICP DAS CAN-2012C CR

Module CANopen Slave 16 kênh đầu vào tương tự AI ICP DAS CAN-2012C CR

CANopen Slave Module with 16bit,16ch AI

Chia sẻ:
Model: CAN-2012C CR
Views: 1153

CANopen is a communication protocol based on the CAN (Controller Area Network) bus. It is mainly used in embedded networks for mechanical control, such as industrial machinery control, vehicle control systems, factory automation, medical equipment control, remote data acquisition, environmental monitoring, and packaging machine control.

The CAN-2012C module complies with the CiA-301 4.02 and CiA-401 2.1 specifications and has been verified by the CiA CANopen compatibility test tool. Therefore, users can easily use CAN-2012C and its EDS files on standard CANopen master software. CAN-2012C has 16-bit, 8-channel differential input or 16-channel single-ended input. Can be applied to many different types of architectures. By using a CANopen master from ICP DAS or other manufacturers, users can efficiently build a CANopen network system.

CPU Module
Watchdog Timer Hardware watchdog
LED Indicators
Status 3 LEDs to PWR, RUN and ERR
Analog Input
Channels 8 Differential or 16 Single-ended (Software Selectable)
Sensor Type ±10V, ±5V, ±2.5V, 0~10V, ±20mA, 0~20mA,4~20mA
Resolution 16-bit
Accuracy +/-0.1% FSR
Sampling Rate 4000 Samples/Sec. (Total)
Input Impedance ≥ 1 MΩ
Common Mode Rejection 84 dB
Overvoltage Protection 70 Vrms
Individual Channel Configuration Yes
Zero Drift ±0.2 μV/ °C
Span Drift ±5 ppm/ °C
CANopen
Baud Rate 10 k ~ 1 M
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Terminal Resistor Built-in 120Ω
Protocol CiA 301 v4.02, CiA 401 v2.1
Node ID 1 ~ 99
No. of PDOs 10 RxPDO , 10 TxPDO
PDO Mode Event Triggered, Remotely requested, Cyclic and acyclic SYNC
Error Control Node Guarding protocol / Heartbeat Producer
NMT Slave
EMCY Message Yes
Power
Consumption 0.5 W
Mechanical
Dimensions (mm) 33 x 99 x 78 ( W x L x H )
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
CAN-2012C     CR  CANopen Slave Module with 16bit,16ch AI (RoHS)
TOP HOME