Module DeviceNet 8 kênh đầu vào tương tự (AI) ICP DAS CAN-2017D CR

DeviceNet Slave Module of 8-ch differential analog Input

Chia sẻ:
Model: CAN-2017D CR
Views: 1047

DeviceNet is one kind of the network protocols based on the CAN bus and mainly used for the embedded network of the machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipments control, remote data acquisition, environmental monitoring, and packaging machines control, etc. The CAN-2017D follows DeviceNet specification Volume I/II, Release 2.0. User can access the analog input status and set the configuration via DeviceNet EDS file. CAN-2017D has 8-channel analog input and it can be used to various applications. By the DeviceNet masters of ICP DAS, you can quickly build a DeviceNet network to approach your requirements. For more information about the DeviceNet master interfaces and other DeviceNet products, please refer to the following web site.

We have communicated with the following DeviceNet masters or gateways.

  1. Allen-Bradley(AB) 193-DNENCAT, 193-DNENCATR
  2. OMRON CJ1W-DRM21
  3. OMRON CS1W-DRM21-V1
  4. OMRON C200HW-DRM21-V1
  5. OMRON 3G8F7-DRM21-E
LED Indicators
Status 1 x Power
2 x DeviceNet status
Analog Input
Channels 8 Differential
Sensor Type ±10V, ±5V, ±1V, ±500mV, ±150mV, ±20mA,( External 125 Ohm Resistor Required)
Resolution 16-bit
Accuracy ±0.1% FSR
Sampling Rate 10 Samples/Sec. (Total)
Input Impedance >2 MΩ
Common Mode Rejection 86 dB
Normal Mode Rejection 100 dB
Overvoltage Protection 240 Vrms
Individual Channel Configuration Yes
Zero Drift ±10 μV/ °C
Span Drift ±25 ppm/ °C
Intra-module Isolation 3000 VDC
DeviceNet
Ports 1
Connection Supported 1 connection for Explicit Messaging
1 connection for Polled I/O
1 connection for Bit-Strobe I/O
Baud Rate 125 kbps, 250 kbps, 500 kbps
Terminal Resistor Switch for 120 Ω terminal resistor
Specification Volume I, Release 2.0 & Volume II, Release 2.0, Errata 5
Node ID 0 ~ 63
Shutdown Message Yes
Heartbeat Message Yes
Subscribe Group 2 Only Server
Power
Input Range +10 VDC ~ +30 VDC
Consumption 2.0 W
Mechanical
Dimensions (mm) 33 x 99 x 78 ( W x L x H )
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 ℃
Storage Temperature -30 ~ +80 ℃
Humidity 10 ~ 90% RH, Non-condensing
CAN-2017D     CR DeviceNet Slave Module of 8-ch Differential Analog Input (RoHS)
TOP HOME