• Industrial Automation
• Industrial Machinery
• Building Automation
• Food and Beverage Systems
• Semiconductor Fabrication
• Control Systems
| CPU Module |
| Watchdog Timer |
Yes, Module (1.6 Seconds), Communication (Programmable) |
| Isolation |
| Intra-module Isolation |
3000 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
±4 kV Contact for Each Terminal
±8 kV Air for Random Point |
| RS Immunity (IEC 61000-4-3) |
±4 kV for Power |
| LED Indicators |
| Status |
1 x Power and Communication |
| Analog Input |
| Channels |
10 Differential or 20 Single-ended (See Note 1), Jumper selectable |
| Range |
±150 mV, ±500 mV, ±1 VDC, ±5 VDC, ±10 VDC, ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (jumper selectable) |
| Resolution |
16-bit |
| Accuracy |
Normal Mode: ±0.1% of FSR
Fast Mode: ±0.5% of FSR |
| Sampling Rate |
Normal Mode: 10 Hz (Total)
Fast Mode: 50 Hz (Total) |
| Bandwidth |
Normal Mode: 15.7 Hz
Fast Mode: 78.7 Hz |
| Input Impedance |
Voltage: 2 MΩ(Differential), 1 MΩ (Single-ended)
Current: 125 Ω |
| Common Mode Rejection |
86 dB |
| Normal Mode Rejection |
100 dB |
| Overvoltage Protection |
Differential: 240 Vrms
Single-ended: 150 Vrms |
| Overcurrent Protection |
50 mA Max. at 110 VDC/VAC Max. |
| Individual Channel Configuration |
Yes |
| Zero Drift |
±20 μV/°C |
| Span Drift |
±25 ppm/°C |
| COM Ports |
| Ports |
1 x RS-485 |
| Baud Rate |
1200 to 115200 bps |
| Data Format |
N, 8, 1 |
| Protocol |
DCON |
| Power |
| Consumption |
0.5 W Max. |
| Mechanical |
| Dimensions (mm) |
31 x 134 x 144 (W x L x H) |
| Environment |
| Operating Temperature |
-25 ~ +75 °C |
| Storage Temperature |
-40 ~ +85 °C |
| Humidity |
10 ~ 90% RH, Non-condensing |
Specification Memo
Note 1: Differential mode can be used for either voltage input or current input. Single-Ended mode can only be used for voltage input.