Thiết bị đo điện thông minh đa kênh 3 pha 8 kênh hoặc 1 pha 24 kênh 100A CANopen ICP DAS PM-4324A-160P-CPS CR

CANopen, Multi-Circuit Power Meter; includes 100A CT

Chia sẻ:
Model: PM-4324A-160P-CPS CR
Views: 876

The PM-4324 series multi-circuit power meter monitors up to 8 three-phase circuits or 24 single-phase circuits, or any combination of single or three-phase circuits. The PM-4324 series can measure up to 24 currents via external Current Transformers (CTs). This flexibility makes the PM-4324 series perfect for multi-tenant facilities such as residential projects, office buildings and shopping malls. This compact instrument is designed to easily fit into existing panelboards or be flush mounted nearby, thus eliminating the need for expensive retrofit projects or for allocating extra space for the device. The PM-4324A is the same model as the PM-4324, except for the AC Measurement. The PM-4324A has 2 separate main circuit inputs that can use in the different power system.

• Generator monitoring
• Switchgear distribution systems
• Energy Management
• Power quality analysis

AC Power Measurement
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Loops 3-phase: 8
1-phase:
24 @ 1P2W-1CT
8 @ 1P3W-2CT
Input Voltage 10 ~ 500 V
Input Current PM-4324A-100P-CPS: CTØ10 mm (0.05 A ~ 60 A)
PM-4324A-160P-CPS: CTØ16 mm (0.1 A ~ 100 A)
PM-4324A-240P-CPS: CTØ24 mm (0.15 A ~ 200 A)
PM-4324A-360P-CPS: CTØ36 mm (0.3 A ~ 300 A)
PM-4324A-400P-CPS: CTØ36 mm (0.3 A ~ 400 A)
Input Frequency 50/60 Hz
W Accuracy Better than 0.5% (PF=1)
Power Parameter Measurement True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh),Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency
Data Update Rate 1 Second
Relay Output
Channels 2
Type Power Relay
Contact Rating Form A:
5 A @ 250 VAC
5 A @ 30 VDC
CANopen
Baud Rate 125 k (default), 250 k, 500 k, 1 M; DIP Switch Selectable
Isolation 3000 VDC
Protocol CANopen
Power
Input Range +85 ~ +264 VAC (277 VAC available)
Consumption 6 W
Mechanical
Casing Metal
Dimensions (mm) 237 x 57 x 134 (W x L x H)
Installation DIN-Rail & wall mounting
Environment
Operating Temperature -20 ~ +70 °C
Storage Temperature -25 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
PM-4324A-160P-CPS     CR  CANopen, Multi-Circuit Power Meter; includes 100A CT (Inside diameter 16 mm; wire lead 4 m) x 24 (RoHS)