Cảm biến đo và lưu trữ PM2.5/Nhiệt độ/Độ ẩm/Điểm sương từ xa kết nối RS-485 + Ethernet ICP DAS CL-210-E CR

PM2.5/Temperature/Humidity/Dew Point Data Logger Module

Chia sẻ:
Model: CL-210-E CR
Views: 1579

Cảm biến đo và lưu trữ PM2.5/Nhiệt độ/Độ ẩm/Điểm sương từ xa ICP DAS CL-210-E CR

The CL-200 series of data logger devices can be used to record PM2.5, CO, CO2, temperature, humidity and dew point information, including the date and time stamps, and are able to store up to 450,000 downloadable records

Real-time data can be accessed from the CL-200 data logger from anywhere and at any time using the free Windows software, the iOS App, or the Android App, as long as they are connected to the same local network as the data logger.

Support is provided for common industrial protocols such as DCON, Modbus RTU, and Modbus TCP, as well as the emerging machine-to-machine (M2M)/)IoT (Internet of Things) connectivity protocol – MQTT. The CL-200 data logger can be connected via widely used communication interfaces including RS-485, Ethernet and PoE, meaning that the device can be easily integrated into existing HMI or SCADA systems, ensuring trouble-free maintenance in distributed control systems

System
Alarm PM2.5/RH/Temperature
Real Time Clock Yes
Data Logger Yes, up to 450,000 records
Temperature Measurement
Range -10 ~ +50°C
Resolution 0.1°C
Accuracy ±0.6°C
Humidity Measurement
Range 0 ~ 100% RH, Non-condensing
Resolution 0.1% RH, Non-condensing
Accuracy ±5% RH, Non-condensing
Dew Point
Range Calculated using temperature and relative humidity
Resolution 0.1°C
PM2.5 Measurement
Range 0 ~ 400 μg/m3
Resolution 1μg/m3
Response Time <= 1 min.
Relay Output
Channels 1 x Form A, SPST
30 VDC @ 16 A or 250 VAC @ 16 A
Ethernet
Ports 10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators)
COM Ports
Ports 1 x RS-485
1 x Ethernet
Protocol DCON and Modbus/RTU (RS-485)
Modbus TCP and MQTT (Ethernet)
Power
Consumption Non-PoE: 2.5 W (Max.)
PoE: 2.65 W (Max.)
Powered from Terminal Block +12 ~ +48 VDC
Mechanical
Dimensions (mm) Ø 150 x 53 (Ø x H)
Installation Ceiling Mounting/Wall Mounting
Ingress Protection Rating IP20
Environment
Operating Temperature 0 ~ 50°C
Storage Temperature -30 ~ +75°C
Humidity 10 ~ 90% RH, Non-condensing
CL-210-E     CR  PM2.5/Temperature/Humidity/ Dew Point Data Logger Module (RS-485, Ethernet PoE) (RoHS)